SilentKnight VisorAlarm Manager User Manual
Page 11

VisorALARM Manager – Quick Guide
11
Doc. DM380-I
Rev. 3.0
Figure 9
STEP 2
Type the name for the default user with management permissions (“manager”) and its
password (“24680”).
STEP 3
Fill out the “IP Address” “IP Mask” and Gateway parameters
STEP 4
Fill out the “General Parameters” and the “Backup configuration” group of params.
If you are configuring a Main receiver select “Main” in the “Type of VisorALARM” box and
fill the “NTP Server” box. (18.145.0.30)
STEP 5
If you have a Serial Printer connected to the WAN2/PRN connector you must enable the
Serial Print Interface checkbox and fill in the transmission parameters.
STEP 6
Fill out the “Internet Link” group of params. This prevents the receiver from generating
“Communication Trouble” signals to each registered mIP/IPDACT device if the Internet link
goes down.
STEP 7
If you have automation software connected to the WAN1/AUT connector you must enable the
“Enable Serial Transmission Configuration” check box and fill in the transmission and
emulation parameters.
STEP 8
If you are going to use the Upload/Download Expansion board you must enable the COM port
used and choose the desired speed.
STEP 9
If you are configuring a equipment member of a cluster in a high availability configuration fill
the “Group Parameters” params. Select the same group identifier for all the equipments of the
a cluster, choose the IP Address for the cluster and the equipment priority. The equipment
with the lower priority in the cluster will be the “active” equipment in a normal situation.