background image

Program Mapping

Appendix D: MS-9600

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

59

Program Mapping

Annunciator points “track” or follow those system points they are
programmed to annunciate; they do not latch. The table outlines the
annunciation of system functions.

Note: Control Switches marked “No Function” will still function as local LAMP TEST
or local ACKNOWLEDGE switches for their respective points.

Table 7 Annunciator Program Mapping - MS-9600

Annunciator

Point

1

ACM-16ATF & AEM-16ATF

ACM-32AF

AEM-32AF

Red LED

Yellow LED

Control Switch

2

Point #1

Indicates System
Alarm

Indicates System
Trouble

ACKNOWLEDGE

Point #2

Not used

Indicates Alarm
Silenced

ALARM SILENCE

Point #3

Not used

Indicates Program
Mode

SYSTEM RESET

Point #4

Not used

Indicates Supervisory

Condition

3

DRILL

Point #5

Not Used

Indicates NAC
Trouble

No Function

Point #6

Not Used

Indicates Walktest

No Function

Point #7

Not Used

Indicates Low Battery

No Function

Point #8

Not Used

Indicates AC Fail

No Function

1. If the Eight-Point Shift (DIP switch # 4) is set “ON,” the eight CPU functions will be shifted from

annunciator points 1 through 8 to points 57 through 64 (provided those points exist in the system).

2. These control switches are active only if: DIP Switch #5 (Receive Only) is ‘OFF’ and DIP Switch

#7 (Switch Inhibit) is ‘OFF’.

3. Supervisory Point lights its associated zone red LED and annunciator point #5 yellow

LED.

This manual is related to the following products: