Program Mapping
Appendix A: Sensiscan 200
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
45
Program Mapping
Annunciator points “track” or follow those system points they are
programmed to annunciate; they do not latch. The table outlines the
annunciation of various system circuits and functions.
Note: Control Switches marked “not used” will still function as local LAMP TEST or
local ACKNOWLEDGE switches for their respective points.
Table 4 Annunciator Program Mapping - Sensiscan 200
Circuit Type
ACM-16ATF & AEM-16ATF
ACM-32AF
AEM-32AF
Red LED
Yellow LED
Control Switch
1
IZ-4F, IZ-4AF,
IZ-8F circuit
Indicates alarm status of
circuit
2
Indicates trouble
status of circuit
Not used
IC-4F, ICE-4F,
ICR-4LF circuit
3
Indicates Activation
Indicates trouble
status of circuit
Controls Notification
Circuit
CR-4F, CRE-4F,
CR-4LF circuit
Indicates Activation
Indicates trouble
status of relay
Controls Relays
TC-2F, TC-4F
circuit
Indicates Activation
Indicates trouble
status of relay
Remote Switch
Functions
Annunciator
Point #1
4
Indicates System Alarm
Indicates System
Trouble
ACKNOWLEDGE
Annunciator
Point #2
Not used
Indicates that signals
have been silenced
SIGNAL SILENCE
Annunciator
Point #3
Not used
Not used
SYSTEM RESET
Annunciator
Point #4
Not used
Indicates Supervisory
condition
Not used
Annunciator
Point #5
Indicates that
Notification Circuit #1
has been activated
Indicates trouble
status of circuit
Controls Notification
Circuit #1
Annunciator
Point #6
Indicates that
Notification Circuit #2
has been activated
Indicates trouble
status of circuit
Controls Notification
Circuit #2
Annunciator
Point #7
Indicates that Remote
Signaling Municipal Tie
has been activated
Indicates trouble
status of circuit
5
Controls Remote
Signaling Municipal
Tie
Annunciator
Point #8
Indicates that Alarm
Relay has been activated
Indicates AC Fail
Controls Alarm Relay
1. These control switches are active only if: DIP Switch #5 (Receive Only) is ‘OFF’ and DIP Switch #7
(Switch Inhibit) is ‘OFF’.
2. With Software P/N #S500R4.0 or higher installed in the Sensiscan 200, the manner in which the
IZ-8Fcircuits programmed as supervisory are annunciated depends upon whether Mode 1 or Mode 2
is selected.
3. ICR-4LF and CR-4LF circuits are annunciated as points 41-44 when installed behind the middle
module or points 49-52 when installed behind the right-hand side module.
4. If the Eight-Point Shift (DIP switch # 4) is set “ON,” the eight CPU functions will be shifted out of
annunciator points 1 through 8. Those eight points will annunciate the first module.
5. Annunciator Point #7 yellow LED indicates Municipal Tie trouble if no UDACT-F is installed. It will
annunciate Low Battery/Ground Fault if a UDACT-F is installed in the system.