ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
53
Appendix C: MS-9200
Capabilities
The MS-9200 allows annunciators to be programmed by zone or by point.
The EIA-485 serial interface will allow up to 32 annunciators, but two-way
communications can occur with only one annunciator per address. The other
devices must be configured as “Receive Only”.
When the panel is programmed by zone, annunciator address 1 is available,
and the annunciator modules display the 56 software zones of the MS-9200.
When the panel is programmed by point, 198 points are available.
Annunciator addresses 1, 2, 3, and 4 can be used, but only address 1 is
supervised.
The furthest annunciator can be 6000 feet from the fire alarm control panel
(check power limitations).
CAUTION: Annunciators on the MS-9200 can not be used for manual
control of Control modules, NACs, or relays (except for global Silence
and Drill switches).
Connecting the EIA-485 Circuit
Communication between the MS-9200 and the annunciator modules is
accomplished over a two-wire EIA-485 serial interface.
• Power-limited and supervised.
• 6000 feet maximum distance (with 16 AWG wire) between the control
panel and the furthest annunciator.
• Use twisted pair cable with a characteristic impedance of
approximately 120 ohms.
• EIA-485 circuit rated 5.5 VDC max., 60 mA max.
This communication circuit is supervised by the MS-9200. Loss of
communication results in “System Trouble” and “Module Failure”
indications at the CPU.
Note: “System Trouble” and “Module Failure” will also occur if the normally closed
supervisory path between TB1 Terminals on the annunciator is opened (or the
jumper has not been installed).
Continued on the next page...
!