3.0 Installation



Securely mount the Model 1600A-N1P enclosure on a suitable panel opening. The recommended opening cut-
size is 9”W X 7.25”H and the required depth is 16”.

8"

10.5"

3.5"

9.75"

Slot Detail

0.375"

R0.109"

0.218"

PLUGTRUB

C

NO

NC

A

B

+

RS-485 VDC

O

I

2A

O

I

2A

O

I

5A

A

B

RS-485

Primary

Second

Out

RE

SE

T

RELAY

COMM

M

S

D

L

S

D

Model 1600A-N1P

Multi-Channel Gas Detection Control System

RELAY

COMM

M

S

D

L

S

D

G

rou

nd

24

VD

C

VA

C (

L1)

NE

U (

L

2)

Figure 3 Unit Mounting and Dimensional


Connect 110/220VAC input wiring to the terminals labeled “ACV (L1)”, “Neutral (L2)”, and “Ground” (See

). The Power Supply is capable of handling AC inputs from 100-240VAC 50-60Hz without

degradation.

Figure 4

Figure 4 AC/DC Inputs

PLUGTRUB

O

I

5A

O

I

2A

O

I

2A

Groun

d

24VD

C

VA

C (L1

)

NE

U (L2

)


If applicable, connect 24 VDC to the terminals labeled “24VDC” and “DC Comm”. This input can be used for
primary power or back-up power in the event of AC power failure.