beautypg.com

Relay activation and configuration, Figure 19 da4 / analog input activation – Detcon 1600A-N1P User Manual

Page 21

background image

1600A-N1P

Figure 19 DA4 / Analog input Activation


Example: In this example, the 1600A is to be set up for two Model DA4 input modules. Make sure that the
switch setting for the first Model DA4 module is set to 01, representing the first gas input and is wired to
terminal connection #1, for position 1 on the module’s wiring connector. The DA4 addresses would be as
follows:

CH #

DA4 Address

01 thru 04

01

05 thru 08

05

4.1.3 Relay Activation and Configuration.


The relay output setup is similar to the gas channel setup. The default setting for the relays as shown in

is for all relays to be in “Off” status. Press the “CH1-4 OFF” key for the CH1-4

box to use the first RL4 module. Note the block now shows as “CH1-4 ON”. The second part of Relay Setup
requires the decision of how the individual relay contacts will be configured. Press the block labeled
“CONFIGURE CH 1-4”, and a relay setup screen will appear. Each relay must be selected as latching or non-
latching, energized or non-energized, and silenceable or non-silenceable. These selections are shown in three
small blocks to the right of the Relay # input. Make selections by pressing the buttons on screen (

). Entries are saved automatically when exiting the screen by pressing MAIN or

Device Setup. Continue this sequence for all other relays.

Figure

21 Activating Relay Outputs

Figure 22

Setting up Relay Outputs


RL 4 Module addresses:
Relay 1-4

41

Relay 5-8

45

Relay 9-12

49

Relay 13-16

4D

1600A-N1P Instruction Manual

Rev. 0.1

Page 17 of 40