1600A-N1P

3) Alarm level(s) for each gas channel
4) Tag Name for each channel
5) Assignment and set-up information for each relay contact

NOTE: The set-up configuration is fully field-programmable and can easily be executed by the user in the
field by following the instructions within this Operators Manual. Modifications to the set-up configuration are
expected to take place at the customer’s site due to requirement changes and/or system expansions.

2.3 Specifications


Capacity
User

Configurable

Up to 16 analog or serial inputs (Model 1600A)

Inputs

Analog 4-20mA (DA-4 Modules)

RS-485 Modbus™ RTU


Outputs
User

Configurable:

Form C Relay Contacts (RL-4 Modules)

4-20mA outputs (AO-4 Modules)

Standard: RS-485


Accuracy/Repeatability

Display: < 1% F.S.

DA-4: < 1% F.S.

AO-4: < 1% F.S.


Power Input
110-230VAC
20-30VDC

Power Consumption

Base 1600A Controller: 20 Watts at 24VDC

Total Power is dependent on number of I/O modules, number of gas sensors, and type of gas sensors

Total power of unit with I/O modules and gas sensors not to exceed 120 Watts


Display

5 inch diagonal Graphic Backlit LCD with Touch screen


Electrical Classification

NEMA 1 Panel Mount


Dimensions

10.5''W x 8''H x 14''D


Operating Temperature Range

0°C to +50°C


Warranty
One

year

1600A-N1P Instruction Manual

Rev. 0.1

Page 3 of 40