Model FP-524D-HRT

FP-524D-HRT Instruction Manual

Rev. 0.1

Page 37 of 48

9) The procedure will return to Step 3. If “End” is selected, the HRT Bridge will exit Loop test and return to

automatic control.

4.4.3.5 HART Setup

The HART Setup Screen allows parameters of the HRT Bridge to be changed or modified. Changes made on
this screen will not be applied until power is cycled on the unit.

Figure 21 HART Setup

 Tag – Text that is associated with the field device installation. This text can be used by the user in any

way. A recommended use is a unique label that correlates to a field device label: a plant drawing, or on
a control system. This variable is also used as a type of data link layer address handle.

 Long Tag – Functions exactly like the Tag except the size is larger (max 32 ISO Latin 1 characters).

 Descriptor – Text that is associated with the field device. This text can be used by the user in any

way. There is no specific recommended use.

 Message – Text that is associated with the field device. This text can be used by the user in any way.

There is no specific recommended use.

 Date – Gregorian calendar date that is stored in the field device. This can be used by the user in any

way. There is no specific recommended use. Note: This field is not updated by the HRT Bridge and
does not indicate the current date.

 Final asmbly num – Number that is used for identification purposes, and is associated with the overall

field device.

 Poll addr – This number is the address of the HRT Bridge on a network and must be set to 0.