Model FP-524D-HRT
FP-524D-HRT Instruction Manual
Rev. 0.1
Page 28 of 48
Figure 15 Primary Variables
Primary Variables
Concentration – the value of the gas concentration measured by the sensor. The units of measurement
(ppm, ppb, or %) are shown to the right of the concentration value. This is the HART primary
variable.
Loop Current – the value of the output 4-20mA loop current
PV %rnge – Primary variable percent of range
EngUnits – the measurement units and gas type
Range Variables
PV LRV – Primary variable lower range value (normally 0 for most sensors)
PV URV – Primary variable upper range value, or the range of the sensor (i.e. 100ppm, 10ppm, 5%,
etc.)
Device Status
Indicates the device has more status information available. If this icon is green, no additional status
information is available. If it is red, refer to Section 4.4.2 Diagnostics for more information.
Measured Values
Concentration – the value of the gas concentration measured by the sensor. The units of measurement
(ppm, ppb, or %) are shown to the right of the concentration value
Temperature – displayed in degrees Centigrade.
PS Voltage – power supply voltage. Nominally 24VDC
PV – Graphic display
A graphic display of the sensor concentration reading may also be displayed in this screen. The graph will be
a graphic display of concentration verses time.