Hygrocontrol manual for type 86 ex page – COSA Xentaur Hygrocontrol Type 86 Ex User Manual
Page 22
20 mA - and the ranges should be set to -50°CTd to +50°CTd and
–20 to +80°C, then the upper limit 50°CTd is set by an output of 8 mA
and the upper limit +80°C is set by an output of 10,4 mA (= 0,08x80 +
4,0)).
Table 3: Adjustment of Dimensiones
-
-
-
-
-
-
-
K
°F
°C
Dimension
Temperature
%rF
open
Enthalpie
Grains
/feet³
Grains
/m³
g/m³
g/kg
°F
Td
°C
Td
%
RH
%
rF
Dimension
Humidity
F
8
7
6
5
4
3
2
1
0
Code
Switch „S1”
Note 3)
If code switch „S1” is turned to a position according to table 3 the new
dimension will be activated if the code bridge "X4" is torn out of
position „K” - but be aware, that the lower and upper limit of the range
which you changed its dimension are still the same as they were
before! You have to adjust them separately!
Example: was the dimension of humidity %RH with a range of 0 to 100%, so
now, after a change of dimension to g/kg, the range will be 0 to 100
g/kg if you don’t change this!
You may quit the „CONFIGURATION” software by putting the code
bridge „X4” back to „M” and turning the code switch „S1” back to position
„0”.
HYGROCONTROL Manual for Type 86 Ex Page
21