A

ppendix

B - ATM i

nsTAllATion

for

A

ccessiBiliTy

B-4

308.3.2 Obstructed High Reach. Where a clear floor or ground space allows a parallel approach to an element and the high side

reach is over an obstruction, the height of the obstruction shall be 34 inches (865 mm) maximum and the depth of the obstruction shall

be 24 inches (610 mm) maximum. The high side reach shall be 48 inches (1220 mm) maximum for a reach depth of 10 inches (255

mm) maximum. Where the reach depth exceeds 10 inches (255 mm), the high side reach shall be 46 inches (1170 mm) maximum for

a reach depth of 24 inches (610 mm) maximum.
EXCEPTIONS:
1. The top of washing machines and clothes dryers shall be permitted to be 36 inches (915 mm) maximum above the finish floor.
2. Operable parts of fuel dispensers shall be permitted to be 54 inches (1370 mm) maximum measured from the surface of the vehicular

way where fuel dispensers are installed on existing curbs.

Figure 308.3.2 Obstructed High Side Reach

ATM i

nsTAllATion

for

A

ccessiBiliTy

1. This document supersedes all other information provided by Triton for ATM installation for accessibility.

2. Information provided in this manual is based on federal guidelines (ADA Accessibility Guidelines for Buildings and Facilities

– ADAAG) as amended through January 1998. You should verify it has not been amended. States may also have accessibility

codes. These codes may be more restrictive than the federal guidelines. Please verify this with the state where the ATM is to be

installed prior to installation. For state contact information, you may call the ADA information line at 1-800-514-0301.

3. For countries other than the US, please use the guidelines for accessibility for that country.

4. A complete copy of the ADAAG referred to here can be found at http://www.access-board.gov. Included in this document is the

section of the ADAAG specifically for ATMs. For additional information on floor surfaces and other ADAAG requirements,

please see the complete specification.

4.34

Automated Teller Machines.

4.34.1 General. Each automated teller machine machine required to be accessible by 4.1.3 (Accessible Buildings: New

Construction) shall be on an accessible route and shall comply with 4.34 (Automated Teller Machines).

4.34.2 Clear Floor Space. The automated teller machine shall be located so that clear floor space complying with 4.2.4 (Clear

Floor or Ground Space for Wheelchairs) is provided to allow a person using a wheelchair to make a forward approach, a

parallel approach, or both to the machine.

4.34.3 Reach Ranges.

(1) Forward Approach Only. If only a forward approach is possible, operable parts of all controls shall be placed within the

forward reach range specified in 4.2.5 (Forward Reach).

(2) Parallel Approach Only. If only a parallel approach is possible, operable parts of controls shall be placed as follows: