Installation, Commander 500 cummins – Lincoln Electric IM707 Commander 500 User Manual

Page 15

background image

A-7

INSTALLATION

COMMANDER 500 CUMMINS

A-7

2. Take necessary steps to assure load is limited to the

capacity of the Commander by installing a 50 amp,
240 VAC double pole circuit breaker. Maximum rated
load for each leg of the 240 VAC auxiliary is 50
amps. Loading above the rated output will reduce
output voltage below the allowable -10% of rated
voltage which may damage appliances or other
motor-driven equipment and may result in overheat-
ing of the COMMANDER 500 CUMMINS engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type 14-

50) to the double-pole circuit breaker using No. 6, 4
conductor cable of the desired length. (The 50 amp,
120/240 VAC plug is available in the optional K802R
plug kit.)

4. Plug this cable into the 50 Amp 120/240 Volt recep-

tacle on the COMMANDER 500 CUMMINS case
front.

Figure A.2 Connection of the COMMANDER 500 CUMMINS to Premises Wiring

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

50AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE