Hired-Hand Super-Savers (Forced Air Heaters) XL: SS-225-XL User Manual
Page 3

4801-5101
Rev
6-09
Page
3
of
26
Super Saver XL CE Heater
Adjustable
Wrench
Gas Leak Testing
Pipe Glue
¼ in. (7 mm.) Nut Driver
Install screw hooks with hammer or drill.
BE SURE TO CHECK DELIVERY!
Locate packing slip and make sure all of the listed
parts are enclosed. If not, call your Hired-Hand
Distributor immediately.
Table Of Contents
1.
Specifications And Requirements..................3
2.
Warnings And Cautions .................................4
3.
Maintenance And Warranty ...........................5
4.
Installation......................................................6
5.
User Instructions ............................................8
6.
Gas/Air Requirements .................................10
7.
Conversion To Other Gases ........................10
8.
Component And Wiring Diagram .................13
9.
Ladder Type Schematic Diagram ................14
10.
Servicing Instructions...................................15
11.
Pipe Sizing For Sufficient Gas Service........20
12.
Parts & Assemblies......................................22
1. Specifications And Requirements
Model No.
Maximum Input
Ventilation
SS-225-XL
65.9 kW (225,000 BTUH)
1700 m
3
/h (1000 CFM)
Butane & Propane
Gas:
Maximum 57.5 mbar (22.7 in. w.c.) and minimum 25 mbar (9.9 in. w.c.) inlet gas
supply pressure acceptable at heater input. Burner manifold pressure 25 mbar (10
in. w.c.) at maximum input. Gas pressure should be checked by certified gas
technician while heater is in operation. All sealing devices must be restored after the
gas conversion. Refer to Section 6. Gas/Air requirements.
Natural Gas:
Maximum 25 mbar (9.9 in. w.c.) and minimum 17 mbar (6.7 in. w.c.) inlet gas
pressure acceptable at heater input. Burner manifold pressure 9.45 mbar (3.8 in.
w.c.) at maximum input. Gas pressure should be checked by a certified gas
technician while heater is in operation. All sealing devices must be restored after the
gas conversion. Refer to Section 6. Gas/Air requirements.
LHV Natural Gas
Maximum 30 mbar (11.9 in. w.c.) and minimum 20 mbar (7.9 in. w.c.) inlet gas
supply pressure acceptable at heater input. Burner manifold pressure 14.1 mbar
(5.6 in. w.c.) at maximum input. Gas pressure should be checked by a certified gas
technician while heater is in operation. All sealing devices must be restored after the
gas conversion. Refer to Section 6. Gas/Air requirements.
Refer to heater ratings plate for unit voltage, amperage, and frequency ratings.
READ ALL INSTRUCTIONS BEFORE YOU START ASSEMBLING
HEATER DIMENSIONS
WEIGHT
60 kG (130 lb.)
HEIGHT
76.2 cm (30 in.)
WIDTH
62.2 cm (24½ in.)
DEPTH
48.9 cm (19¼ in.)
MINIMUM CLEARANCES
Measured From
Inches
mm
Ceiling 12
305
Wall 12
305
Floor 20
500
Livestock must not be allowed to contact
heater or come within 3 meters (10 feet)
of hot air discharge