Fan replacement in a Brocade VDX 6740T and Brocade VDX 6740T-1G

5

show chassis

show environment power

The power supply status can also be viewed using the Web Tools application.

Fan replacement in a Brocade VDX 6740T and Brocade VDX
6740T-1G

The Brocade VDX 6740T and Brocade VDX 6740T-1G have five fans as displayed in

Figure 17

. The

Network OS identifies the fan locations from left to right as fan #1, fan #2, fan #3, fan #4, and fan
#5 when viewed from the non-port side of the switch.

FIGURE 17

Brocade VDX 6740T and Brocade VDX 6740T-1G fan assemblies on the non-port side

ATTENTION

Maintain all power supplies and fans in operational condition to provide redundancy.

CAUTION

Because the cooling system relies on pressurized air, do not leave any of the power supply or fan
slots empty longer than two minutes while the switch is operating. If a power supply or fan
assembly fails, leave it in the switch until it can be replaced.

CAUTION

Disassembling any part of the power supply or fan assembly voids the warranty and regulatory
certifications. There are no user-serviceable parts inside the power supply or fan assembly.

1

Fan #1

4

Fan #4

2

Fan #2

5

Fan #5

3

Fan #3

6

Captive screw (same location for each fan)