STANDARD CFM BLOWER

HIGH CFM BLOWER

A

A

A

B

Standard CFM Blower Air Filter Size Requirements

Number of Filters Required

Unit Input

16 x 20 (in)

20 x 20 (in)

100 MBH (29.3 kW)

4

150 MBH (44.0 kW)

4

200 MBH (58.6 kW)

4

250 MBH (73.2 kW)

4

300 MBH (87.9 kW)

4

2

350 MBH (102.6 kW)

4

2

400 MBH (117.2 kW)

6

500 MBH (146.5 kW)

4

600 MBM (175.8 kW)

4

2

700 MBM (205.1 kW)

4

2

800 MBH (234.4 kW)

6

High CFM Blower Air Filter Size Requirements

Number of Filters Required

Unit Input

16 x 20 (in)

20 x 20 (in)

100 MBH (29.9 kW)

8

150 MBH (44.0 kW)

8

200 MBH (58.6 kW)

8

250 MBH (73.2 kW)

8

300 MBH (87.9 kW)

8

4

350 MBH (102.6 kW)

8

4

400 MBH (117.2 kW)

12

500 MBH (146.5 kW)

8

600 MBH (175.8 kW)

8

4

700 MBH (205.1 kW)

8

4

800 MBH (234.4 kW)

12

1,200 MBH (351.6kW)

12

Figure 18

AIR BLOWER
Belt Tension Adjustment Standard CFM Blower belt
tension can be adjusted by loosening motor mounting
bolts marked A (See Figure 18). To tighten belt, slide
motor down motor mounting bracket and re-fasten motor
to mounting bracket.

High CFM Blower belt(s) tension can be adjusted by
fi rst loosening motor mounting plate bolts marked A
(See Figure 18). To tighten belt tension, turn belt tension
adjustment screws marked B (See Figure 18) counter-
clockwise. To loosen belt tension, turn clockwise. Once
belt tension has been adjusted, re-fasten motor mounting
plate bolts.