STANDARD CFM BLOWER
HIGH CFM BLOWER
A
A
A
B
Standard CFM Blower Air Filter Size Requirements
Number of Filters Required
Unit Input
16 x 20 (in)
20 x 20 (in)
100 MBH (29.3 kW)
4
150 MBH (44.0 kW)
4
200 MBH (58.6 kW)
4
250 MBH (73.2 kW)
4
300 MBH (87.9 kW)
4
2
350 MBH (102.6 kW)
4
2
400 MBH (117.2 kW)
6
500 MBH (146.5 kW)
4
600 MBM (175.8 kW)
4
2
700 MBM (205.1 kW)
4
2
800 MBH (234.4 kW)
6
High CFM Blower Air Filter Size Requirements
Number of Filters Required
Unit Input
16 x 20 (in)
20 x 20 (in)
100 MBH (29.9 kW)
8
150 MBH (44.0 kW)
8
200 MBH (58.6 kW)
8
250 MBH (73.2 kW)
8
300 MBH (87.9 kW)
8
4
350 MBH (102.6 kW)
8
4
400 MBH (117.2 kW)
12
500 MBH (146.5 kW)
8
600 MBH (175.8 kW)
8
4
700 MBH (205.1 kW)
8
4
800 MBH (234.4 kW)
12
1,200 MBH (351.6kW)
12
Figure 18
AIR BLOWER
Belt Tension Adjustment Standard CFM Blower belt
tension can be adjusted by loosening motor mounting
bolts marked A (See Figure 18). To tighten belt, slide
motor down motor mounting bracket and re-fasten motor
to mounting bracket.
High CFM Blower belt(s) tension can be adjusted by
fi rst loosening motor mounting plate bolts marked A
(See Figure 18). To tighten belt tension, turn belt tension
adjustment screws marked B (See Figure 18) counter-
clockwise. To loosen belt tension, turn clockwise. Once
belt tension has been adjusted, re-fasten motor mounting
plate bolts.