Sterling MS User Manual
Page 13

— 13 —
DUCT CONNECTIONS
All ductwork must be properly supported so that no strain 
is put on the unit. Do not alter or bend the discharge duct 
fl anges supplied on your make-up air unit.
Duct connections must have a removable access panel 
in the duct which is connected to a duct furnace. The 
duct openings shall be accessible when the unit is 
installed in service, and shall be of such size that smoke 
or refl ected light may be observed inside the casing to 
indicate the presence of leaks in the heating element. 
The covers for the panels shall be attached in such a 
manner as to prevent leaks. Ducts (or optional outside air 
hoods) exposed to the outdoors must be insulated and 
sealed to prevent water from entering either the unit or 
building through the duct.
If a single, double or triple duct furnace only unit is 
connected to a return air duct, or any other inlet air 
restriction, the appliance shall be installed on the positive 
pressure side of the air circulating blower.
When connecting return air duct to Standard or High 
CFM cabinets, attach duct to return air opening fl ange 
when no dampers are used. Otherwise, if dampers are 
used, attach return air duct around collar at bottom of 
damper assembly. Also refer to the Dimensional Data 
section of this manual, Submittal Data Sheets and Indoor 
Duct Furnace Manual specifi ed for your unit.
GAS PIPING††
All gas piping must be installed in accordance with local 
codes. It is required that a ground union be installed 
adjacent to the gas valve of each duct furnace, and 
a ground union be installed just external of each duct 
furnace for unit servicing. On vertical runs, a drip leg 
should be provided upstream of any control manifold. A 
gas shutoff valve should be, or may be required by local 
codes, installed upstream of the external ground union 
for each duct furnace. A 1/8" N.P.T. plugged tapping, 
accessible for test gauge connection, must be installed 
immediately upstream of the unit gas supply connection.
The open end of piping systems being
purged shall not discharge into areas where there are 
sources of ignition or into confi ned spaces UNLESS 
precautions are taken as follows: (1) By ventilation of 
the space, (2) control of purging rate, (3) elimination 
of all hazardous conditions. All precautions must be 
taken to perform this operation in a safe manner!
 
†† For complete Gas Piping installation, see the 
Separated Combustion Indoor Gas-Fired Duct 
Furnace Installation and Service Manual.
To avoid equipment damage or
possible personal injury, do not connect gas 
piping to this unit until a supply line pressure/
leak test has been completed. Connecting the 
unit before completing the pressure/leak test may 
damage the unit gas valve and result in a fi re hazard.
Do not rely on a gas shutoff valve to
isolate the unit while conducting gas pressure/leak 
tests. These valves may not be completely shutoff, 
exposing the unit gas valve to excessive pressure, 
resulting in damage. 
Do not over-tighten the inlet gas piping
at unit gas valve or stresses that could crack the valve 
may result. 
Never use an open fl ame to detect
gas leaks. Explosive conditions may exist which 
would result in personal injury or death.
The gas line should be supported so that no strain is 
placed on the unit. Pipe compounds which are not soluble 
to liquid petroleum gases must be used on threaded joints.
The appliance and its individual shutoff valve must be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping 
system by closing the individual manual shutoff valve during 
any pressure testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig (3.5 kPa).
For additional gas piping information, including pipe sizing 
and drip leg installation, refer to Separated Combustion 
Indoor Gas-Fired Duct Furnace Installation and Service 
Manual.
For additional piping information, refer to the National 
Fuel Gas Code Z233.1 (latest edition).
NOTICE: If the gas duct furnace is to be fi red with LP gas, 
consult local LP gas dealer for piping size information.
NOTICE: Unit installation for use with propane (bottled) 
gas must be made by a qualifi ed LP gas dealer or 
installer. He will insure proper joint compounds are 
used for making pipe connections; that air is purged 
from lines; that a thorough test is made for leaks before 
operating the unit; and that it is properly connected to 
propane gas supply system.
Before any connection is made to an existing line supplying 
other gas appliances, contact the local gas company to 
make certain that the existing line is of adequate size to 
handle the combined load.
Check all connections for leaks with soap solution.
