Yokogawa Removable Chassis DX1000N User Manual
Page 20
20
IM 04L41B01-03E
Alarm Output Relay Action When the Alarm ACK Operation Is Executed
WO Set alarm and DO settings
Set the Output Relay
Syntax
WO p1,p2,p3,p4,p5
p1 DO type (RLY)
p2 Relay number
NONE No AND setting
I01 Specify only I01
I01-Ixx Specify I01 to Ixx
xx={02 to 36}
p3 Energize/De-energize the relay
DE_ENERGIZE
ENERGIZE
p4 Hold/Not hold the relay
NONHOLD
HOLD
p5 Relay action on ACK
NORMAL
RESET
Example No AND operation of the output relay, relay action is energize, and release
the relay output when the alarm ACK operation is performed regardless of the
alarm status.
WORLY,NONE,ENERGIZE,HOLD,RESET
Section 3.6, “Basic Setting Commands” in the communication interface user’s manual
Settings on the DX: Page 9
Communication Commands