beautypg.com

Yokogawa ADMAG AXF User Manual

Page 58

background image

IM 01E20C01-01E

6-29

6. PARAMETER DESCRIPTION

[G40: Operation Time] Display of operation time
This parameter is used to display the operation time.
The operation time is the total time that is counted
while the device works actually.
When the power supply is off, the operation time is not
counted.
For example, “1D23:45” indicates an operation time of
1 day, 23 hours, and 45 minutes.

IMPORTANT

Use this value as a rough guideline because the
operation time has an error.

[G41: Alm Record1] Alarm record1
This parameter is used to display the most-recent
alarm, and the alarms that can be displayed are as
follows.

Alarm Items

T0637.EPS

Item

Description

No issuing of alarms

Microprocessor (CPU) failure

EEPROM failure

A/D converter failure (at high frequency side)

A/D converter failure (at low frequency side)

A/D converter failure (detection of adhesion)

Flowtube coil is open-circuit

EEPROM returns to default values

Power supply is off.

Instantaneous power fail for tens of
milliseconds.
After this fail is released, outputs reach
the previous value immediately.

The return from excessive instantaneous
noise.
After the noise is released, output return
the normal condition.
Input signal error

Flowtube is not filled with fluid

Insulation adhered to electrode

: 16 space characters

(i.e., no display)

10 : uP Fault

11 : EEPROM Fault

12 : A/D(H) Fault

13 : A/D(L) Fault

14 : A/D(Z) Fault

15 : Coil Open

16 : EEPROM Dflt

18 : Power off

19 : Inst Pwr Fail

28 : WDT

30 : Sig Overflow

31 : Empty Pipe

33 : Adhesion Alm

NOTE

Records for “30: Sig Overflow” are kept only
when G31 specifies that this condition is to be
recognized as an alarm (i.e., “Yes” is selected).
Records for “31: Empty Pipe” are kept only when
G32 specifies that this condition is to be recog-
nized as an alarm (i.e., “Yes” is selected).
Records for “33: Adhesion Alm” are kept only
when G34 specifies that this condition is to be
recognized as an alarm (i.e., “Yes” is selected).

[G42: Alm Record Time1] Display the operation
time of alarm record1
This parameter is used to display the operation time at
which the alarm indicated by G41: Alm Record1
was occurred. For example, “1D23:45” indicates that
an alarm was occurred at the operation time of 1 day,
23 hours, and 45 minutes.

IMPORTANT

Use these values as a reference because the
time of alarm records (1 to 4) have an error.

[G43: Alm Record2] Alarm record2
This parameter is used to display the second most-
recent alarm, and the alarms that can be displayed are
the same as those for G41: Alm Record1.

[G44: Alm Record Time2] Display the operation
time of alarm record2
This parameter is used to display the operation time at
which the alarm indicated by G43: Alm Record2
was occurred. For example, “1D23:45” indicates that
an alarm was occurred at the operation time of 1 day,
23 hours, and 45 minutes.

[G45: Alm Record3] Alarm record3
This parameter is used to display the third most-recent
alarm, and the alarms that can be displayed are the
same as those for G41: Alm Record1.

[G46: Alm Record Time3] Display the operation
time of alarm record3
This parameter is used to display the operation time at
which the alarm indicated by G45: Alm Record3
was occurred. For example, “1D23:45” indicates that
an alarm was occurred at the operation time of 1 day,
23 hours, and 45 minutes.

[G47: Alm Record4] Alarm record4
This parameter is used to display the fourth most-
recent alarm, and the alarms that can be displayed are
the same as those for G41: Alm Record1.

[G48: Alm Record Time4] Display the operation
time of alarm record4
This parameter is used to display the operation time at
which the alarm indicated by G47: Alm Record4
was occurred. For example, “1D23:45” indicates that
an alarm was occurred at the operation time of 1 day,
23 hours, and 45 minutes.