Yokogawa ADMAG AXF User Manual
Page 40

IM 01E20C01-01E
6-11
6. PARAMETER DESCRIPTION
(12) Item N (Menu N): Loop Test Setting items
Menu N contains items that are relevant to the execution of loop testing.
T0613.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
N10 Test Mode
(TEST MODE)
N00 Test
(TEST)
W
Normal
Test
Normal
Selects whether mode will be set
to “Normal” or “Test”.
N20 Test SO1
(TEST SO1)
W
Open(Off)
Closed(On)
Open(Off)
Selects the test condition for
SO1 terminal.
N21 Test SO2
(TEST SO2)
W
Open(Off)
Closed(On)
Open(Off)
Selects the test condition for
SO2 terminal.
N22 Test Alarm Out
(TEST ALM OUT)
W
Open(Off)
Closed(On)
Closed(On)
Selects the test condition for
alarm output terminal.
N23 Test SI1
(TEST SI1)
R
Open
Short
Displays the test condition for
SI1 terminal.
N24 Test SI2
(TEST SI2)
R
Open
Short
Displays the test condition for
SI2 terminal.
N60 —
(SELF CHECK)
R
Good
Error
See “6.5 Alarm Functions”.
N11 Test Output Value
(TEST OUT VAL)
W
%
-10 to 110
0
0%
Sets the test output value.
(13) Item P (Menu P): Parameter Protection items
Menu P contains items that are relevant to write protection and passwords.
T0613-1.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
P10 Key Code
(KEY CODE)
P00 Protect
(PROTECT)
W
0 to 9999
0
Parameter of the display restriction
P20 Write Protect
(W PROTECT)
R
No
Yes
No
Displays whether or not overwriting
of parameter data is prohibited.
P21 Enable Wrt Passwd
(ENABLE WRITE)
W
ASCII 8 characters
Sets the correct password so that
write protection function will be
released.
P22 New Password
(NEW PASSWORD)
W
ASCII 8 characters
Sets the password for write protection
funcion
P23 Software Seal
(SOFT SEAL)
R
Break
Keep
Displays whether or not a Joker
password was used (Break).
P60 —
(SELF CHECK)
R
Good
Error
See “6.5 Alarm Functions”.
Keep