Yokogawa ADMAG AXF User Manual
Page 37

IM 01E20C01-01E
6-8
6. PARAMETER DESCRIPTION
T0608-2.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
G14 H/L Alarm Hys
(H/L ALM HYS)
W
%
0
0 to 10
5 %
Sets hysteresis width for high-low
flow rate limit alarm
G20 Alm Out Act Mode
(ALM OUT ACT)
W
Closed(On) Act
Open(Off) Act
Open(Off)
Act
Selects whether alarm output will
be set to “On Active” or “Off Active.”
G22 4-20mA Burn Out
(4-20 BURNOUT)
R
High
Low
—
Displays the current output
during a CPU failure.
G30 Alm-Setting
(ALM-SETTING)
W
No
Yes
Yes
Selects whether a setting alarm is
to be specified as an alarm.
G31 Alm-Sig Over
(ALM-SIG OVER)
W
No
Yes
Yes
Selects whether a signal overflow
alarm is to be specified as an alarm.
G32 Alm-Emp Pipe
(ALM-EMP PIPE)
W
No
Yes
Yes
Selects whether an empty pipe alarm
is to be specified as an alarm.
G33 Alm-HH/LL
(ALM-HH/LL)
W
No
Yes
No
Selects whether a flow rate
high-high or low-low alarm is
to be specified as an alarm.
G34 Alm-Adhesion
(ALM-ADHESION)
W
No
Yes
No
Selects whether an electrode adhesion
alarm is to be specified as an alarm.
G40 Operation Time
(OPERATE TIME)
R
0D 00:00 to
99999D 23:59
Operation time
G42 Alm Record Time1
(ALM TIME 1)
R
0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the most recent alarm.
G43 Alm Record2
(ALM RECORD2)
R
Same as G41
(Alm Record 1)
Displays the content of the second
most recent alarm.
G44 Alm Record Time2
(ALM TIME 2)
R
0D 00:00 to
99999D 23:59
Displays the operation time at occurrence
of the second most recent alarm.
G45 Alm Record3
(ALM RECORD3)
R
Same as G41
(Alm Record 1)
Displays the content of the third most
recent alarm.
G46 Alm Record Time3
(ALM TIME 3)
R
0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the third most recent alarm.
G47 Alm Record4
(ALM RECORD4)
R
Same as G41
(Alm Record 1)
Displays the content of the fourth
most recent alarm.
G48 Alm Record Time4
(ALM TIME 4)
R
0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the fourth most recent alarm.
G60 —
(SELF CHECK)
R
Good
Error
See “6.5 Alarm Functions”.
G21 4-20mA Alarm Out
(4-20 ALM OUT)
W
2.4mA or Less
4.0mA
Hold
21.6mA or More
21.6mA or
More
Selects the current output during
alarm occurrence.
G41 Alm Record1
(ALM RECORD1)
R
10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
15:Coil Open
16:EEPROM Dflt
18:Power Off
19:Inst Pwr Fail
28:WDT
30:Sig Overflow
31:Empty Pipe
33:Adhesion Alm
Displays the content of the most
recent alarm.