Yokogawa ADMAG AXF User Manual
Page 34

IM 01E20C01-01E
6-5
6. PARAMETER DESCRIPTION
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
T0604-2.EPS
C60 —
(SELF CHECK)
See “6.5 Alarm Functions”.
Good
Error
R
m/s
3
C44 Velocity Check
(VELOCITY CHK)
Display of the span setting using
flow velocity (m/s).
0.000 to 99.999
R
C45 Density Unit
(DENSITY UNIT)
Sets units for density when mass
flow rate is selected.
kg/m
3
lb/gal
lb/cf
W
kg/m
3
C45
0 to 4
C46 Mass Flow Density
(MASS DENSITY)
Sets density when mass flow rate
is selected (with units from C45).
0 to 32000
W
0
C47 User Span Select
(USER SPN SEL)
Selects whether or not special
units are used for flow rate units.
No
Yes
W
No
C48 Flow User Unit
(FL USER UNIT)
Sets the special flow rate units.
8 alphanumeric
characters
W
C48
0 to 4
C49 Flow User Span
(FL USER SPAN)
Sets span when using special flow
rate units.
0.0001 to 32000
W
100
(4) Item D (Menu D): Total Setting items
Menu D contains setting items such as the totalization scale and the forward/reverse totalized values.
T0605.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
D10 Total Unit
(TOTAL UNIT)
W
n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
Pulse/s (*)
Selects the flow rate unit per one
pulse as used for totalization
display. Linked with B30.
D12 Total Decimal Pnt
(TL DECIMAL)
W
0
1
2
3
4
5
6
7
0
Selects position of decimal point
for totalization display
D11 Total Scale
(TOTAL SCALE)
W
0 to 32000
D10
(B30)
0 to 4
0 (*)
Sets the flow rate per one pulse
for the totalization display.
Linked with B31.
Sets the range in vicinity of 0%
within which the totalization
display will be halted.
D13 Total Low Cut
(TOTAL LOWCUT)
W
0 to 100
%
0
3 %
Sets the totalization preset value
in the lower 6 digits of the 8-digit
totalized value.
D21 Ttl Set Val Lower
(TL SET VAL L)
W
0 to 999999
0
0
Sets the totalization preset value
in the upper 2 digits of the 8-digit
totalized value.
D22 Ttl Set Val Upper
(TL SET VAL U)
W
0 to 99
0
0
Sets the totalization switch value
in the lower 6 digits of the 8-digit
totalized value.
D23 Ttl Switch Lower
(TL SWITCH LO)
W
0 to 999999
0
0
Sets the totalization switch value
in the upper 2 digits of the 8-
digits totalized value.
D24 Ttl Switch Upper
(TL SWITCH UP)
W
0 to 99
0
0
Selects whether or not special
units are used as totalized units.
D30 Ttl User Select
(TL USER SEL)
W
No
Yes
No
Sets the special totalized units.
D31 Ttl User Unit
(TL USER UNIT)
W
8 alphanumeric
characters
See “6.5 Alarm Functions”.
D60 —
(SELF CHECK)
R
Good
Error
Executes “Start” or “Stop” of the
totalization function, or executes
“Preset Total” or “Preset Rev
Total”.
D20 Total Execution
(TOTAL EXEC)
W
Start
Stop
Preset Total
Preset Rev Total
Start
D00 Total Set
(TOTAL SET)