A2.5.2 Determining the Output Value

The value of OUT.Value is determined as follows:

᭹ For counting up

OUT = integration start value (0) + Total

᭹ For counting down

OUT = integration start value (TOTAL_SP) -

Total

OUT_TRIP(#14):0

OUT_PTRIP(#15):0

OUT_TRIP(#14):1

OUT_PTRIP(#15):1

Counting up starting from 0

• For counting up

PRE_TRIP(#31)

OUT_TRIP(#14):0

OUT_PTRIP(#15):0

OUT_TRIP(#14):0

OUT_PTRIP(#15):1

OUT_TRIP(#14):1

OUT_PTRIP(#15):1

• For counting down

Counting down starting from TOTAL_SP

PRE_TRIP(#31)

0

0

TOTAL_SP(#7)

TOTAL_SP(#7)

FA0205.EPS

OUT_TRIP(#14):0

OUT_PTRIP(#15):1

Total: Total of integrated values. This value is
retained even if INTEG_TYPE is changed during
integration
(in AUTO).

If OUT is rewritten in the MAN mode, integration
starts with the value rewritten in MAN mode after the
mode was returned to AUTO.

The values in OUT_TRIP and OUT_PTRIP are
determined according to the correlation between OUT
and TOTAL_SP/PRE_TRIP.

For counting up, the OUT value is as follows:

᭹ OUT < TOTAL_SP - PRE_TRIP

⇒OUT_TRIP = 0, COUT_PTRIP = 0

᭹ TOTAL_SP - PRE_TRIP <= OUT <

TOTAL_SP
⇒OUT_TRIP = 0, COUT_PTRIP = 1

᭹ TOTAL_SP <= OUT

⇒OUT_TRIP = 1, COUT_PTRIP = 1

For counting down, the OUT value is as follows:

᭹ PRE_TRIP < OUT

⇒OUT_TRIP = 0, COUT_PTRIP = 0

᭹ 0 < OUT <= PRE_TRIP

⇒OUT_TRIP = 0, COUT_PTRIP = 1

᭹OUT <= 0

⇒OUT_TRIP = 1, COUT_PTRIP = 1

Note that the given conditions do not apply to the
following cases:

• If INTEG_TYPE is 5, 6, or 7, OUT_TRIP and

OUT_PTRIP always output "0."

• If INTEG_TYPE is 1 or 3, occurrence of

AutoRESET (reset caused if the threshold is
exceeded) causes OUT_TRIP to hold "1" for five
seconds.