IM 01E20F02-01E

A-48

APPENDIX 6. SOFTWARE DOWNLOAD

A6.10

Comments on System/Network Management VFD Parameters
Relating to Software Download

IMPORTANT

Do not turn off the power to a field device immediately after changing parameter settings. Data writing
actions to the EEPROM are dual redandant to ensure reliability. If the power is turned off within 60
seconds after setup, the parameters may revert to the previous settings.

(1) DWNLD_PROPERTY

TA0109.EPS

Sub

Index

Element

Size

(Bytes)

Description

Download Class

Indicates the download class.

1: Class 1

1

1

Write Rsp Returned For

ACTIVATE

Indicates whether a write response is returned to the ACTIVATE

command.

1: Write Response Returned

1

2

Write Rsp Returned For

PREPARE

Indicates whether a write response is returned to the PREPARE

command.

1: Write Response Returned

Reserved

(Reserved)

ReadyForDwnld Delay Secs

Indicates the maximum delay after receipt of the

PREPARE_FOR_DWNLD command to proceed to transition from

DWNLD_NOT_READY to DWNLD_READY.

Activation Delay Secs

Indicates the maximum delay after receipt of the ACTIVATE command to

proceed to transition from DWNLD_OK to DWNLD_NOT_READY.

1

1

2

2

6

5

4

3