5.4 AI Function Block Parameters

AI Function block parameters can be read or set from
the host. Figure5.4.1 presents the diagram of AI
Function block.

MODE_BLK.Actual

OUT

AUTO

Direct

F0502.eps

Indirect

Filter

PV_FTIME

Alarms

HI,HI_HI

LO,LO_LO

PV.Value

=1 (Enable)

IO_OPTS.Low cutoff

LOW_CUT

L_TYPE

Ind.Sqr Root

Scaling

OUT_SCALE

SIMULATE.Enable

FIELD_VAL.Value

Scaling

XD_SCALE

/100

✓/100

Disable

Enable

Simulate

SIMULATE.Transducer

Value

Simulate

SIMULATE.Simulate

Value

Figure 5.4.1 Diagram of AI Functional Block

For a list of the parameters of blocks held by the
ADMAG AXF, refer to "List of parameters for each
block of the ADMAG AXF" in Chapter 8. The
following is a list of important parameters with a guide
how to set them.

TAG_DESC, MODE_BLK:

Indicates the three types of function block modes;
Out_Of_Service, Manual, and Auto. TAG_DESC
indicates what mode of operation is desired for AI
Function block. In Out_Of_Service (O/S) mode, the AI
block does not operate. The Manual mode does not
allow values to be updated. The Auto mode causes the
measured value to be updated. Under normal circum-
stances, set the Auto mode to take effect. For
MODE_BLK the Auto mode is the factory default.

CHANNEL:

This is the parameter of the transducer block to be
input to the AI block. AI block is assigned flow rate.