A1.2 Setting and Change of

Basic Parameters

This section describes the procedure taken to set and
change the parameters for each block. Obtaining access
to each parameter differs depending on the configura-
tion system used. For details, refer to the instruction
manual for each configuration system.

Access the block mode (MODE_BLK) of each block.

Set the MODE_BLK

(*Note 1)

to Auto, Man or O/S

(*Note 2)

according to the Write Mode of the parameter to be set or
changed.

FA0101.EPS

Access the parameter to be set or changed.

Make setting or change in accordance with each parameter.

Set the Target of block mode (MODE_BLK) back to Auto

(*Note 2)

.

IMPORTANT

Do not turn the power OFF immediately after
parameter setting. When the parameters are
saved to the EEPROM, the redundant process-
ing is executed for the improvement of reliability.
If the power is turned OFF within 60 seconds
after setting of parameters, changed parameters
are not saved and may return to their original
values.
When the consecutive parameter setting to the
multiple parameters is not executed via the
acyclic data exchange, the time inverval between
each parameter setting must not be within 2
seconds.
Changed parameters may not be written to the
device.

Note 1:Block mode consists of the following four modes that are

controlled by the universal parameter that displays the
operating condition of each block.

- Target: Sets the operating condition of the block.
- Actual: Indicates the current operating condition.
- Permit: Indicates the operating condition that the block is

allowed to take.

- Normal: Indicates the operating condition that the block will

usually take.

Note 2: The followings are the operating conditions which the

individual blocks will take.

AI Function

Block

IT

Function

Block

DI

Function

Block

AR

Function

Block

PID

Function

Block

Automatic (Auto)

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Manual (Man)

Out of Service (O/S)

Transducer

Block

Resource

Block

Yes

Yes

Yes

Yes

TA0102.EPS

Refer to the "List of parameters for each block of the ADMAG AXF" for details of the Write Mode for each block.