beautypg.com

Warning – Yokogawa EJA530E User Manual

Page 16

background image

<2. Handling Cautions>

2-9

IM 01C25F01-01E

b. ATEX Flameproof Type

Caution for ATEX flameproof type.

Note 1. Model EJX/EJA-E Series pressure

transmitters with optional code /KF22 for

potentially explosive atmospheres:

• No. KEMA 07ATEX0109 X

• Applicable Standard: EN 60079-0:2009,

EN 60079-1:2007, EN 60079-31:2009

• Type of Protection and Marking Code:

Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db

• Group: II

• Category: 2G, 2D

• Enclosure: IP66/IP67

• Temperature Class for gas-poof:

T6, T5, and T4

• Ambient Temperature for gas-proof:

–50 to 75°C (T6), –50 to 80°C (T5), and

–50 to 75°C (T4)

• Maximum Process Temperature (Tp.) for

gas-proof:

85°C (T6), 100°C (T5), and 120°C (T4)

• Maximum Surface Temperature for dust-

proof:

T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)

* –15°C when /HE is specified.

Note 2. Electrical Data

• Supply voltage: 42 V dc max.

• Output signal: 4 to 20 mA

Note 3. Installation

• All wiring shall comply with local installation

requirement.

• The cable entry devices shall be of a certified

flameproof type, suitable for the conditions of

use.

Note 4. Operation

• Keep the “WARNING” label attached to the

transmitter.

WARNING: AFTER DE-ENERGIZING,

DELAY 5 MINUTES BEFORE OPENING.

WHEN THE AMBIENT TEMP.≥65°C, USE

HEAT-RESISTING CABLE AND CABLE

GLAND ≥90°C.

• Take care not to generate mechanical

sparking when accessing to the instrument

and peripheral devices in a hazardous

location.

Note 5. Special Conditions for Safe Use

WARNING

• Electrostatic charge may cause an exlosion

hazard. Avoid any actions that cause the

gerenation of eletrostatic charge, such as

rubbing with a dry cloth on coating face of the

product.

• In the case where the enclosure of the

Pressure Transmitter is made of aluminium,

if it is mounted in an area where the use of

category 2D apparatus is required, it shall

be installed in such a way that the risk from

electrostatic discharges and propagating

brush discharges caused by rapid flow of

dust is avoided.

• The instrument modification or parts

replacement by other than an authorized

Representative of Yokogawa Electric

Corporation is prohibited and will void the

certification.

• To satisfy IP66 or IP67, apply waterproof

glands to the electrical connection port.

c. ATEX Intrinsically Safe Type/ATEX

Flameproof Type

Model EJX/EJA-E Series pressure transmitters

with optional code /KU22 or /V1U1 can

be selected the type of protection ATEX

Flameproof, Intrinsically Safe. Ex ia, or Ex ic for

use in hazardous area.

Note 1. For the installation of this transmitter,

once a particular type of protection is

selected, any other type of protection

cannot be used. The installation must be in

accordance with the description about the

type of protection in this user’s manual.

Note 2. For combined approval types Once a

device of multiple approval type is installed,

it should not be re-installed using any

other approval types. Apply a permanent

mark in the check box of the selected

approval type on the certification label on

the transmitter to distinguish it from unused

approval types.

This manual is related to the following products: