Calibrating the Series 96
Warm up the unit (20 minutes). To enter a calibration menu, enter the Factory Page by holding
down the
ˆ and ‰ keys for six seconds. Once in the Factory Page [Fcty] use the Up-arrow ¿ or
Down-arrow ¯ Key to select a menu. The last three menus on the Factory Page are Calibration 1
Menu [cin1], Calibration 2 Menu [cin2] and Process Output Calibration Menu [cout].
You can restore the original factory calibration with Restore Factory Calibration [`rSt]
(Calibration 1 Menu) or revert to the default parameter range selections with Default Settings
[dFLt] (Calibration 1 Menu).
Figure 3 – The Calibration Menus.
[CUSt]
Custom Menu
[FctY]
Factory Page
[Fcty]
Factory Page
[`rSt]
Restore Factory Calibration
[dFLt]
Default Settings
[tc50]
Thermocouple Calibration, 50mV
[tc00]
Thermocouple Calibration, 0mV
[tc32]
Thermocouple Calibration, 32mV
[`gnd]
Set Ground
[LEAd]
Lead Resistance Calibration
[r`15]
RTD Calibration, 15
Ω
[r380]
RTD Calibration, 380
Ω
[A`0u]
Process Calibration 1, 0V
[A10u]
Process Calibration 1, 10V
[A`4A]
Process Calibration 1, 4mA
[A20A]
Process Calibration 1, 20mA
[Fcty]
Factory Page
[b`0u]
Process Calibration 2, 0V
[b10u]
Process Calibration 2, 10V
[b4A`]
Process Calibration 2, 4mA
[b20A]
Process Calibration 2, 20mA
[Fcty]
Factory Page
[1``4]
Output Calibration 1, 4mA
[1`20]
Output Calibration 1, 20mA
[1``1]
Output Calibration 1, 1V
[1`10]
Output Calibration 1, 10V
[2``4]
Output Calibration 2, 4mA
[2`20]
Output Calibration 2, 20mA
[2``1]
Output Calibration 2, 1V
[2`10]
Output Calibration 2, 10V
[4``4]
Output Calibration 4, 4mA
[4`20]
Output Calibration 4, 20mA
[4``1]
Output Calibration 4, 1V
[4`10]
Output Calibration 4, 10V
‰
‰
¿
[`LOC]
Lockout Menu
[FctY]
[dIAg]
Diagnostics Menu
[FctY]
[cin1]
Calibration 1 Menu
[FctY]
[cin2]
Calibration 2 Menu
[FctY]
‰
[cout]
Process Output Calibration Menu 1
[FctY]
¯
¿
¯