Watlow Series 96 Calibration Manual, 1/16 DIN Temperature Controller User Manual
Page 10
1 0
■
C a l i b r a t i o n
Wa t l o w S e r i e s 9 6
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1619 w
4.00 (400)
0.00 to 99.99
[4``4] Output Calibra-
tion 4, 4mA
Enter the output
value in milliamps
as measured.
Active if output 2 is process (96 _
_ - _ F _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1612 w
10.00 (1000)
0.00 to 99.99
[2`10] Output Calibra-
tion 2, 10V
Enter the output
value in volts as
measured.
Active if output 2 is process (96 _
_ - _ F _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1611 w
1.00 (100)
0.00 to 99.99
[2``1] Output Calibra-
tion 2, 1V
Enter the output
value in volts as
measured.
Active if output 2 is process (96 _
_ - _ F _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1610 w
20.00 (2000)
0.00 to 99.99
[2`20] Output Calibra-
tion 2, 20mA
Enter the output
value in milliamps
as measured.
Active if output 2 is process (96 _
_ - _ F _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1609 w
4.00 (400)
0.00 to 99.99
[2``4] Output Calibra-
tion 2, 4mA
Enter the output
value in milliamps
as measured.
Active if output 1 is process (96 _
_-F _ _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1607 w
10.00 (1000)
0.00 to 99.99
[1`10] Output Calibra-
tion 1, 10V
Enter the output
value in volts as
measured.
Active if output 1 is process (96 _
_-F _ _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1606 w
1.00 (100)
0.00 to 99.99
[1``1] Output Calibra-
tion 1, 1V
Enter the output
value in volts as
measured.
Active if output 1 is process (96 _
_-F _ _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1605 w
20.00 (2000)
0.00 to 99.99
[1`20] Output Calibra-
tion 1, 20mA
Enter the output
value in milliamps
as measured.
Active if output 1 is process (96 _
_-F _ _ _-_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1604 w
4.00 (400)
0.00 to 99.99
[1``4] Output Calibra-
tion 1, 4mA
Enter the output
value in milliamps
as measured.
[cout]
Process Output
Calibration Menu
[Fcty] Factory Page