Ordering information – Watlow Series 96 Calibration Manual, 1/16 DIN Temperature Controller User Manual
Page 11
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1622 w
10.00 (1000)
0.00 to 99.99
[4`10] Output Calibra-
tion 4, 10V
Enter the output
value in volts as
measured.
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1621 w
1.00 (100)
0.00 to 99.99
[4``1] Output Calibra-
tion 4, 1V
Enter the output
value in volts as
measured.
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1620 w
20.00 (2000)
0.00 to 99.99
[4`20] Output Calibra-
tion 4, 20mA
Enter the output
value in milliamps
as measured.
Wa t l o w S e r i e s 9 6
C a l i b r a t i o n
■
1 1
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Address
Parameters to Appear
Read/Write
Ordering Information
(1551)
Series 96
9 6 — — – — — — — – — — — —
Microprocessor-based
1
/
16
DIN with universal input 1.
Options include software, power supply,
input 2, four outputs and display color
Power Supply
A
= 100-240V
ı
(ac/dc)
B
= 24-28V
ı
(ac/dc)
Input 2
0
= None
1
= Event input & 0-5V
Î
(dc)/
4-20mA (remote set point input)
Output 1
C
= Switched dc/open collector
D
= Electromechanical relay, Form C,
2A, without RC suppression
F
= Universal Process, range selectable: 0-20mA,
4-20mA, 0-5V
Î
(dc), 1-5V
Î
(dc), 0-10V
Î
(dc)
K
= 0.5A solid-state relay without
RC suppression
Output 2
A
= None
C
= Switched dc output/open collector
D
= Electromechanical relay, Form C, 2A, without RC suppression
F
= Universal Process, range selectable: 0-20mA,
4-20mA, 0-5V
Î
(dc), 1-5V
Î
(dc), 0-10V
Î
(dc)
K
= 0.5A solid-state relay without
RC suppression
Output 3
A
= None
D
= Electromechanical relay, Form C, 2A, without RC suppression
Output 4
A
= None
D
= Electromechanical relay, Form C, 2A, without RC suppression
R
= 232 Communications
U
= 485 Communications
M
= Universal Retransmit, range selectable: 0-20mA,
4-20mA, 0-5V
Î
(dc), 1-5V
Î
(dc), 0-10V
Î
(dc)
Software/Preset Parameters
00
= Standard software
AA = Ramping
Display/Overlay
Upper/Lower
RR = Red/Red display
GR =
Green/Red display
RG = Red/Green display
GG =
Green/Green display