FP-3710K Series User Manual
5-4
•
Be sure that the ambient operating temperature and the surrounding operating humidity are within their
designated ranges. (When installing the FP in a cabinet or an enclosure, “Ambient operation temperature”
indicates both the panel face and cabinet or enclosure's internal temperature.).
•
Be sure that heat from surrounding equipment does not cause the FP to exceed its standard operating tem-
perature.
•
When installing the FP in a slanted panel, the panel face should not incline more than 30
o
.
•
When installing the FP in a slanted panel, and the panel face inclines more than 30
o
, the ambient tempera-
ture must not exceed 40
o
C. You may need to use forced air cooling (fan, A/C) to ensure the ambient oper-
ating temperature is 40
o
C or below.
Panel Face
Inside of the
enclosure
Unit: mm
[in.]
100
[3.94]
100
[3.94]
30
[1.18]
30
[1.18]
Ambient Operating Temperature: 0 to 50
o
C
Surrounding Operating Humidity:10 to 90%RH
No more than 30 degrees of tilt