Installation prerequisites for standards – Proface FP3900 - 19 Flat Panel" User Manual
Page 11
![background image](/manuals/358993/11/background.png)
10
Installation prerequisites for standards
•
UL listed products
•
c-UL listed products
•
Product List
UL/c-UL File No.: E220851, E210412
For the detailed certification's information, refer to the Pro-face Home page.
•
The FP must be used as a built-in component of an end-use product.
•
This unit should be installed in the front face of a metal panel.
•
If this unit is installed so as to cool itself naturally, be sure to install it in a vertical panel.
Also, be sure that the FP unit is mounted at least 100 mm away from any adjacent structures or equipment. If these
requirements are not met, the heat generated by the FP unit’s internal components may cause the unit to fail to meet
UL/c-UL standard requirements.
•
For use in Pollution Degree 2 environment
•
For use on a flat surface of a Type 4X (Indoor Use Only) and/or Type 12 Enclosure.
•
Type 4X (Indoor Use Only) and/or 12 Enclosure, when the hatch for Front USB Port is secured by screw.
Type 1 Enclosure, when the hatch for Front USB Port is open.
•
Receivable signals are only from isolated secondary source.
•
All interface ports (except for Front USB Connector (Type A) ) are not intended to be directly connected to a signal
source greater than 30 volts and available current greater than 5mA.
Industrial Control Equipment
refer to UL508
see [a] in the
“Product List“
Suitable for use in Class I, Division 2,
Groups A, B, C, and D Hazardous (clas-
sified) locations, or Non-Hazardous
Locations.
refer to
ANSI/ISA 12.12.01
see [b] in the
“Product List“
Process Control Equipment
refer to CSA-C22.2
No.142
see [c] in the
“Product List“
Suitable for use in Class I, Division 2,
Groups A, B, C, and D Hazardous (clas-
sified) locations, or Non-Hazardous
Locations.
refer to
CSA-C22.2 No. 213
see [d] in the
“Product List“
Product Model No.
Registration Model
No.
UL
c-UL
[a]
[b]
[c]
[d]
FP3710-K41-U
3620004-01
9
9
9
9