REV 1 CT-3500 S2 USER’S MANUAL
27
3.5.6. Timing a Special OPEN Operation
Some special circuit breakers are designed in such a way that two of the dry-contacts follow the
breaker operation while the third contact operates in the opposite direction. For example,
when an OPEN operation is performed, two of the dry-contacts open while the third contact
closes. The CT-3500 S2 offers a special OPEN test that can be used to time such a breaker.
Follow the steps below to perform a special OPEN operation:
a. Start from the “START-UP” menu:
Press the
[1]
key (TIME BRKR).
b. The following screen will be displayed:
Press the
[5]
key (SP OPEN).
c. The following screen will be displayed:
Manually initiate an OPEN operation on the breaker.
TEST: OPEN
OPEN BREAKER NOW...
TIMING MODE:
1.OPEN 2.CLOSE
3.OPEN-CL 4.CL-OPEN
5. SP OPEN
1. TIME BRKR 05/16/12
2. GET RSLT 09:55:55
3. SETUP
4. DIAGNOSTICS
- Resistor Transducer Adapter 9095-UC (7 pages)
- Accu-Ohm 200 S2 (4 pages)
- Accu-Trans (28 pages)
- ATO-400 (43 pages)
- ATO-400P (44 pages)
- Auto-Ohm (22 pages)
- Auto-Ohm 100_200 s2 (31 pages)
- Auto‐Ohm 200 S3 (66 pages)
- DMOM-100 (35 pages)
- DMOM-100_200 s2 (42 pages)
- DMOM-200 (33 pages)
- Herculito (17 pages)
- ATRT-01 S2 (59 pages)
- ATRT-01_01B S3 (88 pages)
- ATRT-01_01B_01D (31 pages)
- ATRT-03_03A (114 pages)
- ATRT-03_03A S2 (147 pages)
- CVT-765 (46 pages)
- Tri-Phase (155 pages)
- CBCT (14 pages)
- CBPS-300 (16 pages)
- CT-3500 (24 pages)
- CT-6500 (69 pages)
- CT-6500 S2 (82 pages)
- CT-7000 (83 pages)
- CT-7000 S2 (108 pages)
- CT-7000 S3 (137 pages)
- CT-7500 (76 pages)
- CT-7500 S2 (110 pages)
- CT-8000 (120 pages)
- CT-8000 S3 (145 pages)
- DigiTMR (86 pages)
- DigiTMR S2 (123 pages)
- DigiTMR S2 PC (31 pages)
- MCCB-250 (17 pages)
- UPS S2 (13 pages)
- EZCT-2000 (68 pages)
- EZCT-2000 (45 pages)
- EZCT-2000A (103 pages)
- EZCT-2000B (118 pages)
- EZCT-2000C Plus (119 pages)
- EZCT-S2 (66 pages)
- EZCT-S2A (98 pages)
- IRM-5000P (58 pages)