REV 1 ATRT-01/01B S3 USER’S MANUAL

5

1.2.2. ATRT-01B S3 Technical Specifications

Table 2. ATRT-01B S3 Technical Specifications

TYPE

Transformer Turns Ratio Tester

PHYSICAL SPECIFICATIONS

Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm)
Weight: 9 lbs (4.3 Kg)

INPUT POWER 90 to 240 Vac, 50/60 Hz

Battery: SLA battery delivering up to 4 hours of continuous operation per
charge.

MEASURING METHOD

ANSI/IEEE C57.12.90

RATIO MEASURING RANGE

0.8 - 15,000 (5 digit resolution)

TURNS-RATIO ACCURACY

40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%)
4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%)

TEST VOLTAGE

4 Vac @ 500mA, 40 Vac @ 70mA

PHASE ANGLE

MEASUREMENT

0 - 360 degrees, Accuracy ±0.2 degree (±1 digit)

POLARITY READING

In-Phase or Out-of-Phase indication

EXCITATION CURRENT

READING RANGE

0-2 Amperes, Accuracy: 2% of reading (±1 mA)

DISPLAY

Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels

COMPUTER INTERFACE

RS-232C

PC SOFTWARE Windows XP/Vista/7 Transformer Analysis Software (included with purchase)

INTERNAL TEST RECORD

STORAGE

128 records of 33 readings

EXTERNAL TEST RECORD

STORAGE

Up to 999 test records on external USB Flash drive.

SAFETY Designed to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2

standards

ENVIRONMENT Operating: -10ºC to 50ºC (15ºF to +122ºF)

Storage: (-30ºC to 70ºC (-22ºF to +158ºF)

HUMIDITY (MAX) 90% RH @ 40˚ C (104˚ F) non-condensing

ALTITUDE (MAX) 2000m (6562 ft) to full safety specifications

CABLES One 15 ft. (4.6m) Single phase cable, one power cord, one cable bag

OPTIONS Transportation Case (Can hold unit and cables)

WARRANTY One year on parts and labor

NOTE

The above specifications are valid at nominal operating voltage and at a
temperature of 25

°C (77°F). Specifications may change without prior notice.