beautypg.com

Vanguard ATRT-01_01B S3 User Manual

Page 36

background image

ATRT-01/01B S3 USER’S MANUAL

REV 1

32

Line 1 of the results shows the Phase A test results, and line 2 shows the Phase B test
results.

Press the

[ENTER]

key to continue.

j. The following screen will be displayed showing the Phase C cable connections for the

selected test:

Make the cable connections per the instructions and then press the

[START]

key to

run the Phase C test.

k. The following screen will be displayed while the test is being performed:

The Phase A, B, and C test results will be displayed on the LCD screen when testing has
finished:

The phase angles for Phase A, B, and C are also displayed at the bottom of the test
results from left to right, respectively. Press any key to continue.

TEST RESULTS:

RATIO MA

%DIFF

A +15.003 001 0.02
B +15.015 001 0.10
C +15.000 001 0.00
181.4

° 183.2° 181.8°

XFMR TYPE: DYN1

TESTING:
DYN1 phase C





PHASE C

CABLE XFMR
X1,X2 to x3,x0
h1,h2 to h3,h2


"START" when READY

RATIO MA

%DIFF


+15.003 001 0.02
+15.015 001 0.10


"ENTER" TO CONTINUE..