Vanguard ATRT-01_01B S3 User Manual
Page 34
ATRT-01/01B S3 USER’S MANUAL
REV 1
30
Type the X winding name plate voltage value using the numeric keypad. The
screen will be updated as shown:
Press the
[ENTER]
key. Continue to step f.
2. NO
Press the
[2]
key (NO) if you do not want to enter the transformer name plate
voltage. Continue to step f.
3. USE PREV DATA
Press the
[3]
key (USE PREV DATA) to use the name plate voltage values entered
when performing the last test. Continue to step f.
f. The following screen will be displayed momentarily:
Then the following screen will be displayed showing the Phase A cable connections for
the selected test (this will differ depending on the test selected):
PHASE A
CABLE XFMR
X1,X2 to x1,x0
h1,h2 to h1,h3
"START" when READY
TESTING AT 40 VOLTS
NAME PLATE VOLTAGE:
H : X
500 : 10
NAME PLATE VOLTAGE:
H : X
500 : 0
- Resistor Transducer Adapter 9095-UC (7 pages)
- Accu-Ohm 200 S2 (4 pages)
- Accu-Trans (28 pages)
- ATO-400 (43 pages)
- ATO-400P (44 pages)
- Auto-Ohm (22 pages)
- Auto-Ohm 100_200 s2 (31 pages)
- Auto‐Ohm 200 S3 (66 pages)
- DMOM-100 (35 pages)
- DMOM-100_200 s2 (42 pages)
- DMOM-200 (33 pages)
- Herculito (17 pages)
- ATRT-01 S2 (59 pages)
- ATRT-01_01B_01D (31 pages)
- ATRT-03_03A (114 pages)
- ATRT-03_03A S2 (147 pages)
- CVT-765 (46 pages)
- Tri-Phase (155 pages)
- CBCT (14 pages)
- CBPS-300 (16 pages)
- CT-3500 (24 pages)
- CT-3500 S2 (53 pages)
- CT-6500 (69 pages)
- CT-6500 S2 (82 pages)
- CT-7000 (83 pages)
- CT-7000 S2 (108 pages)
- CT-7000 S3 (137 pages)
- CT-7500 (76 pages)
- CT-7500 S2 (110 pages)
- CT-8000 (120 pages)
- CT-8000 S3 (145 pages)
- DigiTMR (86 pages)
- DigiTMR S2 (123 pages)
- DigiTMR S2 PC (31 pages)
- MCCB-250 (17 pages)
- UPS S2 (13 pages)
- EZCT-2000 (68 pages)
- EZCT-2000 (45 pages)
- EZCT-2000A (103 pages)
- EZCT-2000B (118 pages)
- EZCT-2000C Plus (119 pages)
- EZCT-S2 (66 pages)
- EZCT-S2A (98 pages)
- IRM-5000P (58 pages)