Installation instructions iqview../rpm, 1 installation - mounting, Connect power – TREND IQView.._RPM User Manual
Page 3: Do not switch on, Route cables, Connect rs232

3
IQView../RPM Installation Instructions TG200712 Issue 1/F 10/01/07
Installation Instructions
IQView../RPM
Connect Power
7
WARNING: This apparatus must be earthed (grounded)
(via supply earth (ground) terminal)
DO NOT
SWITCH ON
0
I
3 2 1
1
LINK
RS232
Rx Tx
OK
28-36 V
24 V
ETHERNET
OK
DATA
R+ R- T+ T-
7 6 5 4
28 to 36 Vdc or 24 Vac ±10 %, 50/60 Hz
terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
28 - 36 V
24 V ~
24
Vac
24 Vac
E
28
Vdc
+28V
0V
E
3.1 Installation - Mounting
(continued)
Route Cables
6
3 2 1
1
LINK
RS232
Rx Tx
OK
28-36 V
24 V
ETHERNET
OK
DATA
R+ R- T+ T-
7 6 5 4
rear view of
connector
~
IQView consumption <= 24 VA maximum (13 VA typical).
The IQView consumes 13VA, but the input power supply
should be capable of 24 VA to cater for startup current.
WARNING
Do not attempt to supply power through
the RS232 connector (as is done with
NDP). This will damage the unit.
!
230 Vac
L
N
E
24 Vac
E
ACC/24VAC
L
N
24 Vac
E
PSR/230/24-2.5
L
N
E
28 Vdc
E
0 V
using 230V/24V ac
transformer with one
side earthed (grounded)
100 to 240 Vac
using 230V/24V ac
transformer with isolated
output (e.g. ACC/24VAC)
using 28 Vdc power supply
(e.g. PSR/230/24-2.5)
230 Vac
Connect RS232
8
3 2 1
1
LINK
RS232
Rx Tx
OK
28-36 V
24 V
ETHERNET
OK
DATA
R+ R- T+ T-
7 6 5 4
only connection for IQView Mono,
if required for IQView (standard version)
IQ1xx or CNC with 25 Way D type female
IQ3, IQ2xx, (some IQ1xx with RJ11)
IQ1xx with 5 in line plug
3 2 1
1
LINK
RS232
Rx Tx
OK
28-36 V
24 V
ETHERNET
OK
DATA
R+ R- T+ T-
7 6 5 4
3 2 1
1
LINK
RS232
Rx Tx
OK
28-36 V
24 V
ETHERNET
OK
DATA
R+ R- T+ T-
7 6 5 4
3 2 1
1
LINK
RS232
Rx Tx
OK
28-36 V
24 V
ETHERNET
OK
DATA
R+ R- T+ T-
7 6 5 4
IQ3xcite, IQ2xx, IQ1xx
IQ1xx, CNC
IQ1xx
IQView
IQView
IQView
RJ11
CABLE/EJ105650 (supplied with IQView
Mono, not IQView standard version)
RJ11
RJ11
CABLE/EJ105651
25 way
D male
RJ11
CABLE/EJ105651
CABLE/78-1772
(additional)
5 in line socket
WARNING
Do not attempt to supply power through the
RS232 connector (as is done with NDP).
This will damage the unit.
!