T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 1/C 25/06/07

5

Installation Instructions

T/PI

Installation

(continued)

Remove Lid

5

Wire to Controller

8

Insert Cable

7

either use M20 flexible conduit

or use M16 cable gland

Remove Connector

6

IQ1xx, IQ2xx

polarity independent

Sensor

24 Vdc

IN

Terminate screen at IQ end only

Analogue input
channel linked

for current (I)

I

IQ system TP/I/22/HF/200
(Belden 8761) cable
recommended.
Terminal size 0.5 to 2.5 mm

2

(14 to 20 AWG)

IQ3

Sensor

0 (0 V)

N (in)

Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to
C (+24V), instead connect to AUX+ (+24V).

+ (24 V)

Caution: This unit contains static

sensitive devices. Suitable
anti-static precautions
should be taken throughtout
the operation to prevent

damage to the units. BS EN100015/
1 Basic Specification: protection of
electrostatic sensitive devices.