Commissioning – LEESON SM4 Series Flux Vector User Manual
Page 28

27
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P121
P122
P123
p124
TB-13A Input
Function
TB-13B Input
Function
TB-13C Input
Function
TB-13D* Input
Function
0
0 None
Disables input
1 AUTO Reference: 0-10 VDC
For frequency mode, see P160...P161,
For PID mode, see P204…P205,
For vector torque mode, see P330
2 AUTO Reference: 4-20 mA
3 AUTO Reference: Preset
For frequency mode see P131...P137,
For PID mode, see P231…P233,
For torque mode see, P331…P333
4 AUTO Reference: MOP Up
• Normally open: Close input to
increase or decrease speed, PID
setpoint or torque setpoint.
• MOP Up is not active while in STOP
5 AUTO Reference: MOP Down
6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control Select
Use when P100 = 4, 5 to switch
between terminal strip control and
local or remote keypad control.
9 Network Enable
Required to start the drive through
the network.
10 Reverse Rotation
Open = Forward Closed = Reverse
11 Start Forward
See note for typical circuit
12 Start Reverse
13 Run Forward
See note for typical circuit
14 Run Reverse
15 Jog Forward
Jog Forward speed = P134
16 Jog Reverse
Jog Reverse speed = P135
WARNING! Active even if P112 = 0
17 Accel/Decel #2
See P125, P126
18 DC Brake
See P174; close input to override P175
19 Auxiliary Ramp to Stop
Normally closed: Opening input will
ramp drive to STOP according to P127,
even if P111 is set to Coast (0 or 1).
20 Clear Fault
Close to reset fault
21 External Fault
F
.
EF
Normally closed circuit; open to trip
22 Inverse External Fault
F
.
EF
Normally open circuit; close to trip
23 AUTO Ref: Sequence
Segment #1
Works in Speed Mode only
24 Start Sequence
25 Step Sequence
Transition from non-asserted to
asserted state
26 Suspend Sequence
WARNING!
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be
deactivated or a fault condition induced.
NOTE: P124
is
applicable to SMV
15HP (11kW) and
greater models
only