Up down, Accel/decel 2 – KB Electronics KBDA-48 User Manual
Page 46
46
A4.
FORWARD/STOP AND REVERSE/STOP COMMAND
The Multi-Function Input Terminals can be used for remote Forward/Stop and Reverse/Stop operation
by connecting a switch or contact to any Multi-Function Input Terminal “1” – “7”, as shown in Figure
29, on page 47. When the “Forward/Stop” switch or contact is closed, the drive will run in the forward
direction and when the switch or contact is opened, the drive will stop. When the “Reverse/Stop”
switch or contact is closed, the drive will run in the reverse direction and when the switch or contact
is opened, the drive will stop.
Set Run/Stop-Forward/Reverse Control (Function No. 1.00) to External Contacts (“0001”). Set the
respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06), which will be used for
“Forward/Stop”, to “0006”. Set the respective Multi-Function Input Terminal (Function Nos. 7.00 –
7.06), which will be used for “Reverse/Stop”, to “0007”. In Figure 29, on page 47, Multi-Function Input
Terminals “4” and “7” have been arbitrarily chosen.
FIGURE 27 – UP/DOWN FREQUENCY CONTROL SWITCH OR CONTACT CONNECTIONS AND FUNCTION SETTINGS
14
4
16
1
15
TB1
2
17
3
18
9
21
5
19
6
20
7
22
8
23
26
10
24
11
25
12
27
13
28
Up Down
Function Settings
Function No.
Range/Code
2.00
Frequency
Control
0005
Up/Down
Using MFITs
7.03
Multi-Function
Input Terminal 4
0003
Up Frequency
Command
7.04
Multi-Function
Input Terminal 5
0004
Down Frequency
Command
7.14
Up/Down Frequency
Control Mode
0000 or 0001
Free-Running or
Incremental
7.15*
Increment of Up/Down
Frequency
0.01 – 30.00 Hz
Set to the Desired
Frequency
* Use with Function No. 7.14 code “0001” only.
A3.
ACCEL/DECEL 2
The drive provides a secondary Accel/Decel Time setting, which can be remotely selected with a
switch or contact connected to any Multi-Function Input Terminal “1” – “7”, as shown in Figure 28.
Set the respective Multi-Function Input Terminal (Function Nos. 7.00 – 7.06) to Accel/Decel 2 (“0005”).
The Accel/Decel 2 time is set in Function No. 7.16 (factory set to 1.5 seconds). When the switch or
contact is closed, the Accel/Decel 2 setting is selected. Accel/Decel 2 overrides the Accel and Decel
settings in Function Nos. 3.03 and 3.04. In Figure 28, Multi-Function Input Terminal “6” has been
arbitrarily chosen.
FIGURE 28 – ACCEL/DECEL 2 SWITCH OR CONTACT CONNECTION AND FUNCTION SETTINGS
16
15
1
TB1
26
21
Accel/Decel 2
17
2
3
18
5
4
19
20
6
22
7
8
23
10
9
24
25
11
14
27
12
13
28
Function Settings
Function No.
Range/Code
7.05
Multi-Function
Input Terminal 6
0005
Accel/Decel 2
7.16
Accel/Decel 2
Time
0.3 – 180.0
Set to the
Desired Time