beautypg.com

KB Electronics KBDA-48 User Manual

Page 4

background image

IMPORTANT APPLICATION INFORMATION

1.

50 Hz Motors – This drive has been factory programmed to operate 60 Hz motors. For 50 Hz motor

operation, set Function No. 0.00 to “0001”. See Figure 16, on page 23.

2.

Motor Current Setting – The motor current for all drive models is factory set to the maximum drive rat-

ing, as shown in Table 3, on page 10. In order for the motor overload protection to operate properly, the

drive must be reprogrammed to the actual motor nameplate current. Use Function No. 0.01 to enter the

motor nameplate current. See Figure 17, on page 24.

a. Model KBDA-27D – Has a maximum current rating of 6.7 Amps (2 HP (1.5 kW)) when used with a

208 – 230 Volt 50/60 Hz AC line input (factory setting of motor current and AC line input voltage).

When used with 115 Volt 50/60 Hz AC line input (Jumper J1 installed in the “115V” position), the

maximum rating of the drive is 5.5 Amps (1

1

2

HP (1.13 kW)). Be sure to reprogram Motor Current

(Function No. 0.01) to the actual motor nameplate current rating (not to exceed 5.5 Amps).

b. Model KBDA-29 – Has a maximum rating of 9.0 Amps (3 HP (2.25 kW)) when used with a 208 – 230

Volt 50/60 Hz 3-phase AC line input. When used with a 208 – 230 Volt 50/60 Hz single-phase AC

line input, the maximum rating of the drive is 6.7 Amps (2 HP (1.5 kW)). Be sure to reprogram Motor

Current (Function No. 0.01) to the actual motor nameplate current rating (not to exceed 6.7 Amps).

4

FIGURE 1 – QUICK-START CONNECTION DIAGRAM

1

1

QUICK-START INSTRUCTIONS

Important: You must read these simplified instructions before proceeding. These instructions are to

be used as a reference only and are not intended to replace the details provided herein. You must

read the Safety Warning on, page 6, before proceeding.

Note: This drive contains bus capacitors, which must be reconditioned if the drive has been in stor-

age for over 1 year. To recondition the bus capacitors, apply the AC line, with the drive in the Stop

Mode, for a minimum of 30 minutes.

see Section 6.1, on page 18.

(Models KBDA-29, 45, 48):

(Terminals "L1", "L2", "L3")

208/230, 400/460 Volt, 3-Phase

2

see Section 6.1, on page 18.

(Models KBDA-24D, 27D, 29):

(Terminals "L1", "L2")

208/230 Volt, Single Phase

2

AC Induction Motor:

see Section 6.3, on page 19.

3-Phase

Motor

W

L1

U

V

MOTOR

TB1

see Section 6.2, on page 19.

Ground (Earth):

see Section 6.2, on page 19.

Ground (Earth):

L3

L2

AC LINE

See Figure 1. Also see Section 4 - Important Application Information, on page 16.

WARNING! HIGH VOLTAGE – Disconnect main power before making connections

to the drive.

Notes: 1. Layout of Models KBDA-24D, 27D

vary slightly. 2. 50/60 Hz AC line input.

This manual is related to the following products: