FUNCTION GROUP 9 – ANALOG INPUT SIGNAL OPERATION
(IODA OPTION BOARD REQUIRED)
Notes: (1) For Analog Input 1 (Function Nos. 9.00 – 9.04), Frequency Control (Function No. 2.00) must be set to Analog Signal 1 (code
“0002”). (2) For Analog Input 2 (Function Nos. 9.05 – 9.09), Frequency Control (Function No. 2.00) must be set to Analog Signal 2 (code
“0003”). (3) For Current Signal Input, set Jumper J1, on the IODA, to the “CUR” position. (4) 0.15 – 1 kHz (0 – 100% duty cycle).
Function
No.
Description
Range/Code
Factory
Setting
9.00
Analog Input 1 Gain (%)
(1)
0 – 500
100
9.01
Analog Input 1 Slope
(1)
0000: Positive
0001: Negative
0000
9.02
Analog Input 1 Offset (%)
(1)
0 – 100
0
9.03
Analog Input 1 Type
(1)
0000: Unidirectional
0001: Bidirectional
0000
9.04
Analog Input 1 Response Time (mSec)
(1)
2 – 100
2
9.05
Analog Input 2 Gain (%)
(2)
0 – 500
100
9.06
Analog Input 2 Slope
(2)
0000: Positive
0001: Negative
0000
9.07
Analog Input 2 Offset (%)
(2)
0 – 100
0
9.08
Analog Input 2 Type
(2)
0000: Analog Voltage or Current
(3)
0001: PWM
(4)
0000
9.09
Analog Input 2 Response Time (mSec)
(2)
2 – 100
2
* Functions which can only be changed while the drive is in the Stop Mode.
FUNCTION GROUP 10 – COMMUNICATION MODE (DIAC OPTION BOARD REQUIRED)
Function
No.
Description
Range/Code
Factory
Setting
10.00*
Assigned Communication Station Number
1 – 247
30
10.01
*
Communications Watchdog Timer
0000: Disabled
0001: Enabled
0000
10.02
*
Watchdog Timeout (Seconds)
0.50 – 2.00
0.50
10.03
Operational Command
0
0: Stop
1: Run
—
1
0: Forward
1: Reverse
2
0: N/A
1: Fault Reset
3
0: JOG-LCL/REM Command Off
1: JOG-LCL/REM Command On
4
0: N/A
1: Preset Frequency 1
5
0: N/A
1: Preset Frequency 2
6
0: N/A
1: Preset Frequency 3
7
0: N/A
1: Preset Frequency 4
8
0: N/A
1: Preset Frequency 5
9
0: N/A
1: Preset Frequency 6
10
0: N/A
1: Preset Frequency 7
11 – 15
Reserved