3. Increase the boost until the ammeter reaches the nameplate rated current (Amps AC).

4. Using the Main Speed Potentiometer, slowly adjust the motor speed over a 0 – 15 Hz

(0 – 450 RPM) range. If the motor current exceeds the nameplate rating, decrease the

boost setting.

13.7 Motor Overload (I

2

t) with RMS Current Limit (CL)* – Sets the current limit (overload), which

limits the maximum current to the motor, prevents motor burnout, and eliminates nuisance

trips. The CL Trimpot is factory set to 160% of the drive rating. To increase the current limit,

rotate the CL Trimpot clockwise. To decrease the current limit, rotate the CL Trimpot counter-

clockwise. See Figures 28 – 32, on page 43.

*UL approved as an electronic overload protector for motors.

In order to ensure that the motor is properly protected with the I

2

t feature, it is required

that the CL Trimpot be set for 160% of the motor nameplate rating. This is accom-

plished as follows:

Note: This adjustment must be made within 6 seconds or the I

2

t Trip will occur.

1. Wire an AC RMS ammeter in series with one motor phase.

2. Set the CL Trimpot fully counterclockwise.

3. Adjust the speed setting to 30% of full speed.

4. Lock the motor shaft and adjust the CL Trimpot to 160% of the motor nameplate rating.

Example: A 1/2 HP motor has a full load current rating of 1.8 Amps. Set the CL Trimpot to

1.8 X 160% = 2.9 Amps.