Step 3: testing the thermostat – Robertshaw 9520 User Manual

Page 7

background image

12. Put the °F/°C switch to either °F for Fahrenheit display

or °C for Celsius display (see Figure 5).

Figure 5

13. Replace cover on thermostat by snapping into place.

14. Turn on power to system . Test thermostat as described

in the following section.

Step 3: Testing the Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR
SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND
VOID YOUR WARRANTY.

CAUTION: D

O NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW

50°F (10°C).

T

HIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY

.

1. Place the COOL-OFF-HEAT-EM

switch into the COOL position

2. Press the

button until the

temperature setting is at east
3 degrees below the room
temperature. The air conditioning
system should turn on within
a few seconds.

NOTE: Once the thermostat turns off when in the COOL mode, a built in 5-
minute delay prevents the system from turning on again. This protects the
compressor. No additional time delay relay is required. To override the 5-
minute delay for installation, press the RESET button.

3. Put the COOL-OFF-HEAT-EM switch

into the OFF position. The air
conditioning system should turn off.

4. Put the COOL-OFF-HEAT-EM switch

into the HEAT position.

7

Batteries NOT Required.

°

F/

°

C Switch

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

>