Robertshaw 9600 User Manual

Page 9

background image

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS
VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE
THE THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: D

O NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW

50°F

(10°C). T

HIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL

INJURY

.

1. Place the COOL-OFF-HEAT

switch into the COOL position.

2. Press the button until the temperature setting is at least 3 degrees

below the room temperature. The air conditioning system should
turn on within a few seconds.

NOTE: T

HERE IS A BUILT IN

5-

MINUTE DELAY ON BREAK FOR COMPRESSOR PROTEC

-

TION

. A

SECOND ATTEMPT TO TURN ON THE AIR CONDITIONING WILL RESULT IN A

5-

MINUTE DELAY IN COMPRESSOR ACTIVATION

.

3. Put the COOL-OFF-HEAT switch into

the OFF position. The air conditioning
system should turn off. The fan may
continue to run for a short period of time.

4. Put the COOL-OFF-HEAT switch

into the HEAT position.

5. Press the button until the temperature setting is at least

3 degrees above room temperature. The heating system should turn
on. The fan may not turn on immediately, depending on the fan delay
built into the furnace.

6. Put the COOL-OFF-HEAT switch

into the OFF position. The heating
system should turn off. Once again,
the fan may have a delay.

7. Put the

AUTO–ON switch

to the ON position. The blower
fan should turn on.

8. Put the

AUTO–ON switch

to the AUTO position. The blower
fan should turn off.

9

COOL-OFF-HEAT

COOL-OFF-HEAT

COOL-OFF-HEAT

AUTO - ON

AUTO - ON

COOL-OFF-HEAT