Maintenance, Routine maintenance – Ransburg EFM & EFMD Solvent Applicator 76480, 76482, 76485, 76488 User Manual
Page 24
![background image](/manuals/348159/24/background.png)
AA-99-01.1
1 9
1 9
1 9
1 9
1 9
EFM(D) Solventborne Robotic Atomizers - Maintenance
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
Good maintenance is essential to safe and
productive operation. Schedules should be
established by the user, based on the following
general information and observations of the initial
production requirements. The ITW Ransburg
maintenance and safety information should be
made available to each operator.
Normal fire protection measures are necessary,
including proper storage of paints and solvents
and the proper disposal of waste. Ready access
to appropriate fire extinguishing equipment is
required. For details, consult the appropriate
NFPA safety information, your local fire codes,
local painting equipment standards. Reference
OSHA, NFPA-33, and your insurance carrier's
information for additional information.
ROUTINE MAINTENANCE
ROUTINE MAINTENANCE
ROUTINE MAINTENANCE
ROUTINE MAINTENANCE
ROUTINE MAINTENANCE
SCHEDULE
SCHEDULE
SCHEDULE
SCHEDULE
SCHEDULE
Follow these maintenance steps to extend the life
of the applicator and ensure efficient operation:
Several Times Daily
Several Times Daily
Several Times Daily
Several Times Daily
Several Times Daily
1. Turn the LECU5004 MicroPak Control Unit
OFF
OFF
OFF
OFF
OFF!
2. Inspect the fluid nozzle and electrode wire for
paint accumulation. Clean as frequently as
necessary. (See "Procedures" in the "Mainte-
nance" section.)
>
An electrical discharge or spark may
create an electrical and/or fire hazard during
maintenance. Do not clean or service the
spray applicator with the power supply on.
Verify that the power supply has been locked
out and tagged out per OSHA.
>
Unexpected robot movement can be
hazardous. Do not adjust or repair the spray
applicator when the robot is operating or wait-
ing to start. The robot must be locked out and
tagged out per OSHA.
>
Solvents used for equipment flushing must
have flash point ratings equal to or greater than
the flash point rating of the coating material.
Solvents used for general cleaning must have
flash point ratings higher than 100
°
F (37.8
°
C).
W A R N I N G
W A R N I N G
W A R N I N G
W A R N I N G
W A R N I N G
!!!!!
>
Take precautions to see that skin is not
punctured by sharp electrode.
W A R N I N G
W A R N I N G
W A R N I N G
W A R N I N G
W A R N I N G
!!!!!
Daily (Or at Shift Start)
Daily (Or at Shift Start)
Daily (Or at Shift Start)
Daily (Or at Shift Start)
Daily (Or at Shift Start)
1. Turn the LECU5004 MicroPak Control Unit
OFF
OFF
OFF
OFF
OFF and:
• Check within 20 feet of the point of operation
(of the applicator) and remove or ground
ALL
ALL
ALL
ALL
ALL loose or ungrounded containers.
• Inspect workholders for accumulated coating
materials (remove such accumulations if
present)
• Check that the nozzle assembly is clean
and undamaged.
• Straighten the applicator electrode if
necessary.
>
Do not bend the applicator electrode while
wiping. Never immerse the applicator in sol-
vents. This will cause damage to the electrical
components.
C A U T I O N
C A U T I O N
C A U T I O N
C A U T I O N
C A U T I O N
!!!!!