Chapter 4 Power Software Configuration tool
Configuring Billing Energy and TOU Registers
50
Multi-Mon
Multiple Circuit Energy Monitor
The available options are shown in the following table:
Parameter
Parameter
Parameter
Parameter
Options
Options
Options
Options
Default
Default
Default
Default
Description
Description
Description
Description
Billing
Billing
Billing
Billing/TOU Registers
/TOU Registers
/TOU Registers
/TOU Registers
TOU
Unchecked
Checked
Unchecked Links tariff registers to the selected energy
source
Use Profl
Unchecked
Checked
Unchecked Enables automatic daily profiling for
energy usage registers (both total and
tariff registers if TOU is enabled)
Dmd Profl
Unchecked
Checked
Unchecked Enables automatic daily profiling for
maximum demand registers (both total
and tariff registers if TOU is enabled)
Sum Profl
Unchecked
Checked
Unchecked Enables daily profiling for summary
registers (total of all tariffs). Automatically
set when profiling is enabled.
Units
kWh, kvarh, kVAh None
The register measurement units. It is set
automatically.
Register Source List
Register Source List
Register Source List
Register Source List
Source
Input
None
kWh IMPORT
kWh EXPORT
kvarh IMPORT
kvarh EXPORT
kVAh TOTAL
Submeter 1 -
Submeter 40
1
None
Links an energy source to the target
register of all metering submeters, or links
all registers of a source submeter to a
totalization submeter.
Multiplier
0.001 to 100.000
0.100
The multiplication factor for the energy
source.
Target
Reg#1- Reg#3
Submeter 1 -
Submeter 40
1
None
Defines the target register for the energy
source. It is set automatically for target
energy registers.
1
Linking a submeter to another totalization submeter connects all its
configured energy registers to the corresponding registers of the target
submeter.