beautypg.com

Teledyne 4030 - Total Hydrocarbon gas analyzer User Manual

Page 50

background image

Operation

Teledyne Analytical Instruments 48

AL-1 20.00 ppb

AL-1 SOURCE THC

AL-2 ACTIVE

AL-2 LOW

AL-2 FAILSAFE

AL-2 LATCHING

AL-2 50.00 ppb

AL-2 SOURCE SMP

________________________________________________

Note: For the purpose of example, Alarm 2 has been set differently

than Alarm 1.

Note: An alarm in 'alarm condition' is signaling that action must be

taken such as correcting the alarm or the analysis concentration. If an
active (not defeated) alarm has been set to HIGH at 20.0 ppb, and the
analysis concentration is above that level, then the 'alarm condition' is
occurring.


DEFEATED: If an alarm is defeated, its relay is de-energized,

regardless of failsafe condition. A defeated alarm does not react to a
transition over its trip point in either direction.

HIGH: If an alarm is set as HIGH, it will not create a new alarm

condition (see latching) if the analysis concentration is below the trip
point, if the analysis concentration is above the trip point, then an alarm
condition will be created or maintained.

FAILSAFE: A non-defeated alarm that is in FAILSAFE mode

energizes an alarm relay in a non-alarm condition and de-energizes an
alarm relay in an alarm condition.

Note: Failsafe condition of an alarm is in software. This is not

related to relays that have both normally-open and normally-closed
terminals.

LATCHING: The latching property configures the alarm such that

the user must manually relieve the alarm condition even though the
concentration no longer violates the trip point of the alarm. So, if an
alarm is NON-LATCHING, and the analysis concentration temporarily
drifts above the trip point of a HIGH alarm, the alarm condition occurs