Notice – Detroit Radiant Products Company FA Series User Manual

Page 43

background image

43

FA

Series

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.

NOTICE

4.0

Troubleshooting Guide

Key

Start

Question

Process

Question

Corrective

Action

Is there 24 VAC

across the ‘R’ and

‘C’ terminals?

Check fuse on circuit board and

internal controls transformer.

After approx.

10 seconds of

operation, is there

a flash code for

‘Pressure Switch

Failure’?

Replace pressure switch after verifying:

• Heater, blower, and venting are clean and

free of obstructions.

• The allowable vent length is not

exceeded.

• There is not a negative pressure

experienced at the area of intake (e.g.,

high winds, attic space, tightly sealed

building).

Replace

circuit board.

Monitor the voltage on

the gas valve terminals

during trial for ignition.

Is there 24 VAC present

during the spark

sequence?

Yes

Gas valve is faulty.

Replace.

No

Yes

Is there 24 VAC

across the ‘W’

and ‘C’ terminals?

Yes

Is the circuit board

sending 120 VAC

to the draft inducer

motor?

Yes

Is the draft

inducer impeller

obstructed or

locked up?

Remove

obstruction.

No

The draft inducer motor is

faulty and must be replaced.

Yes

No

Is the pressure

switch stuck in the

closed position?

Pressure switch is faulty.

No

Yes

Check the

two flame roll

out switches

and the tube

temperature

limit switch. Are

they closed?

Yes

Reset or replace

faulty limit switch.

No

Replace circuit board.

Check for flash

codes on the circuit

board. Replace the

ignition module.

No

No

No

Yes

Repair thermostat or

thermostat wiring.