beautypg.com

Detroit Radiant Products Company FA Series User Manual

Page 39

background image

39

FA

Series

Chart 3.6

High Altitude Conversion Kits for Elevations of 4,501 to 7,000 Feet

Chart 3.7

High Altitude Conversion Kits for Elevations of 7,001 to 9,500 Feet

Figure 3.13

High Altitude Kit Installation

Model

Number of

Orifices

Kit Number

Orifice Size

Natural Gas

Propane

Natural Gas

Propane

FA-100

4

HKN-44_4

HKP-55_4

44 DMS

55 DMS

FA-125

5

HKN-44_5

HKP-55_5

44 DMS

55 DMS

FA-150

6

HKN-44_6

HKP-55_6

44 DMS

55 DMS

FA-175

7

HKN-44_7

HKP-55_7

44 DMS

55 DMS

FA-200

7

HKN-43_7

HKP-54_7

43 DMS

54 DMS

FA-225

9

HKN-44_9

HKP-55_9

44 DMS

55 DMS

FA-250

9

HKN-42_9

HKP-54_9

42 DMS

54 DMS

Model

Number of

Orifices

Kit Number

Orifice Size

Natural Gas

Propane

Natural Gas

Propane

FA-100

4

HKN-45_4

HKN-56_4

45 DMS

56 DMS

FA-125

5

HKN-45_5

HKN-56_5

45 DMS

56 DMS

FA-150

6

HKN-45_6

HKN-56_6

45 DMS

56 DMS

FA-175

7

HKN-45_7

HKN-56_7

45 DMS

56 DMS

FA-200

7

HKN-44_7

HKN-55_7

44 DMS

55 DMS

FA-225

9

HKN-45_9

HKN-56_9

45 DMS

56 DMS

FA-250

9

HKN-43_9

HKN-55_9

43 DMS

55 DMS

3.0

Installation

High Altitude Operation

Sheet Metal

Screws

Gas Orifices

Manifold Pipe

Note: Install gas

orifices to a torque

of 150 in. lbs.

Sheet Metal

Screws