Shutdown Procedures:


Set the thermostat to the lowest setting.

Turn OFF all electrical power to the appliance if service is to be performed.

Turn manual shut off knob clockwise

to OFF.

Do not force.

If the heater’s internal diagnostic LED displays any of the signals listed in Charts 4.1-4.2, address the
indicated problem as outlined.

Chart 4.1 •

LED Diagnostic Codes - United Technologies Circuit Board

Chart 4.2 •

LED Diagnostic Codes - Fenwal Circuit Board

4.0

Operation

Shutdown Procedures

LED CODE

(# of flashes)

GREEN LED STATUS / ERROR

STEADY OFF

Internal Control Fault or No Power

STEADY ON

Control Ok

1

In Lockout from Failed Ignitions or Flame Losses

2

Pressure Switch Open with Inducer ON

3

Pressure Switch Closed with Inducer OFF

4

Limit Switch is OPEN

5

In Lockout from False Flame

LED CODE

(# of flashes)

AMBER LED STATUS / ERROR

FAST FLASH

Flame Present With Gas Valve Off

STEADY ON

Flame is Sensed

LED CODE

(# of flashes)

GREEN LED STATUS / ERROR

SLOW FLASH

Normal Operation - No Call for Heat

FAST FLASH

Normal Operation - Call for Heat

2

Ignition Lockout - No Flame Detected

3

Airflow Fault - Pressure Switch Open or Closed

4

High Limit or Rollout Switch Open

5

Flame Sense Error - Gas Valve Not Energized

STEADY ON

Internal Control Failure

LED CODE

(# of flashes)

AMBER LED STATUS / ERROR

OFF

Flame Signal is Below Required Level / No Flame Present

STEADY ON

Flame is Sensed